EasyManua.ls Logo

AIREDALE DeltaChill - Electrical

AIREDALE DeltaChill
302 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chillers
DeltaChill™ Air Cooled and FreeCool
Introduction
17
Chiller Technical Manual 7267818 V1.13.0_01_2018
Electrical
Electrical Overview
Location of Electrical components within the chiller.
A weatherproof electrical power and controls panel shall be situated at the end of the unit and contains:
Individual mains power isolation for each circuits compressors.
Separate electrical isolation for fans.
Dedicated bus-bar chamber for connection of incoming 3 phase and earth mains power supply.
Emergency stop tted to controls compartment door.
Separate, fully accessible controls compartment allowing adjustment of set points whilst the unit is operational.
Circuit breakers for protection of all major unit components.
Phase rotation relay incorporating phase loss protection.
The electrical power and control panel is wired to the latest European standards and codes of practice.
Mains supply is 3 phase and a neutral is not required, refer to interconnecting wiring.
Separate 230V 1ph 50Hz permanent supply is required for the controls and safety features. Isolator allows for a
maximum cable size of 10 mm.
Electrical terminals for external evaporator pipe work trace heating (230V / 500 Watt) are provided. The external
trace heating is tted by others.
Pumps
Circuit 3
Compressors
Bus-bar Chamber
Fans
Power Factor
Correction
Circuit 1
Compressors
Panel Ventilation
Controls
Circuit 2
Compressors

Table of Contents

Related product manuals