Technical Data
Ecodesign
DCC050DX-14EPV0, DCC052DX-14EYY0, DCC055DX-15DYV0
Notes: Units DCC050DX-14EPV0 DCC052DX-14EYY0 DCC055DX-15DYV0
SEPR
1,3,5 5.77 5.58 5.81
SEPR Tier
Tier 2 (2021) Tier 2 (2021) Tier 2 (2021)
Annual Electricity Consumption
kWh/a 627687 677448 690738
Rated Refrigerant Capacity
P
A
1,3,5 kW 489 510.1 542
Rated Power Input D
A
kW 155.7 168.3 172.6
Rated EER
DC,A
3.14 3.03 3.14
Declared Refrigerant Capacity P
B
1,3,5 kW 545.4 / 446.3 476.8 / 384.8 605.3 / 503.5
Declared Power Input D
B
kW 128.0 / 102.3 114.3 / 89.5 142.2 / 116.3
Declared EER
DC,B
4.26 / 4.36 4.17 / 4.30 4.26 / 4.33
Declared Refrigerant Capacity P
C
1,3,5 kW 480.4 / 371.9 512.4 / 413.6 542.8 / 441.3
Declared Power Input D
C
kW 85.0 / 65.2 95.1 / 74.2 96.9 / 75.8
Declared EER
DC,C
5.65 / 5.71 5.39 / 5.57 5.60 / 5.82
Declared Refrigerant Capacity P
D
1,3,5 kW 497.3 / 384.6 424.5 / 317.8 453.2 / 336.2
Declared Power Input D
D
kW 74.8 / 57.9 66.1 / 50.0 67.7 / 50.6
Declared EER
DC,D
6.65 / 6.64 6.43 / 6.35 6.70 / 6.64
SSCEE
2,3,5 % 175.3 171.6 18%.5
SSCEE Tier
6 Tier 1 (2018) Tier 1 (2018) Tier 2 (2021)
Rated Cooling Capacity P
rated,c
2,4,5 491 512.4 543.6
Declared Cooling Capacity 35°C Pdc
2,3,5 kW 489 510.1 542
Declared EER
d
35°C
3.14 3.03 3.14
Declared Cooling Capacity 30°C Pdc
2,3,5 kW 545.4 / 446.3 476.8 / 384.8 605.3 / 503.5
Declared EER
d
30°C
4.26 / 4.36 4.17 / 4.30 4.26 / 4.33
Declared Cooling Capacity 25°C Pdc
2,3,5 kW 480.4 / 371.9 512.4 / 413.6 542.8 / 441.3
Declared EER
d
25°C
5.65 / 5.71 5.39 / 5.57 5.60 / 5.82
Declared Cooling Capacity 20°C Pdc
2,3,5 kW 497.3 / 384.6 424.5 / 317.8 453.2 / 336.2
Declared EER
d
20°C
6.65 / 6.64 6.43 / 6.35 6.70 / 6.64
Sound Power Level LWA
dB(A) 88 86 87
Air ow rate
m³/h 222501 222501 238393
Off mode P
OFF
kW 0.157 0.157 0.157
Thermostat-off mode P
TO
kW 2.343 2.597 2.043
Standby Mode P
SB
kW 0.289 0.301 0.306
Crankcase heater mode P
CK
kW 0.000 0.000 0.000
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside conguration.
(6)
Please contact Airedale regarding Non Compliant selections