Notes: Units DCF055DX-14DPV0 DCF057DX-14DYY0 DCF059DX-15DYV0
SEPR
1,3,5 6.76 6.63 6.68
SEPR Tier
Tier 2 (2021) Tier 2 (2021) Tier 2 (2021)
Annual Electricity Consumption
kWh/a 548876 581165 598626
Rated Refrigerant Capacity
P
A
1,3,5 kW 500.6 519.7 540.1
Rated Power Input D
A
kW 161.0 172.7 177.1
Rated EER
DC,A
3.11 3.01 3.05
Declared Refrigerant Capacity P
B
1,3,5 kW 563.9 / 461.3 491.2 / 397.9 505.4 / 412.1
Declared Power Input D
B
kW 133.3 / 106.7 117.6 / 92.1 119.9 / 94.4
Declared EER
DC,B
4.23 / 4.32 4.18 / 4.32 4.22 / 4.37
Declared Refrigerant Capacity P
C
1,3,5 kW 501.8 / 387.3 533.8 / 431.5 549.1 / 446.8
Declared Power Input D
C
kW 89.4 / 68.8 98.4 / 76.7 100.2 / 78.5
Declared EER
DC,C
5.61 / 5.63 5.42 / 5.62 5.48 / 5.69
Declared Refrigerant Capacity P
D
1,3,5 kW 396.9 / 260.7 413.2 / 334.9 429.4 / 342.0
Declared Power Input D
D
kW 39.3 / 40.1 42.1 / 50.9 43.4 / 52.1
Declared EER
DC,D
10.10 / 6.49 9.83 / 6.58 9.90 / 6.57
SSCEE
2,3,5 % 167.1 171.6 172.1
SSCEE Tier
6 Tier 1 (2018) Tier 1 (2018) Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5 504.2 522.2 542.7
Declared Cooling Capacity 35°C Pdc
2,3,5 kW 500.6 519.7 540.1
Declared EER
d
35°C
3.11 3.01 3.05
Declared Cooling Capacity 30°C Pdc
2,3,5 kW 563.9 / 461.3 491.2 / 397.9 505.4 / 412.1
Declared EER
d
30°C
4.23 / 4.32 4.18 / 4.32 4.22 / 4.37
Declared Cooling Capacity 25°C Pdc
2,3,5 kW 501.8 / 387.3 533.8 / 431.5 549.1 / 446.8
Declared EER
d
25°C
5.61 / 5.63 5.42 / 5.62 5.48 / 5.69
Declared Cooling Capacity 20°C Pdc
2,3,5 kW 396.9 / 260.7 413.2 / 334.9 429.4 / 342.0
Declared EER
d
20°C
10.10 / 6.49 9.83 / 6.58 9.90 / 6.57
Sound Power Level LWA
dB(A)
Air ow rate
m³/h 201476 201476 215867
Off mode P
OFF
kW 0.157 0.157 0.157
Thermostat-off mode P
TO
kW 4.049 2.940 3.161
Standby Mode P
SB
kW 0.289 0.301 0.306
Crankcase heater mode P
CK
kW 0.000 0.000 0.000
Technical Data
Ecodesign
DCF055DX-14DPV0, DCF057DX-14DYY0, DCF059DX-15DYV0
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside conguration.
(6)