Notes: Units DCF082TX-18GYYY DCF085TX-19HYYV DCF088TX-20HYVV
SEPR
1,3,5 6.39 6.48 6.52
SEPR Tier
Tier 2 (2021) Tier 2 (2021) Tier 2 (2021)
Annual Electricity Consumption
kWh/a 879703 893912 912224
Rated Refrigerant Capacity
P
A
1,3,5 kW 759.2 781.4 802.5
Rated Power Input D
A
kW 268.3 271.3 275.8
Rated EER
DC,A
2.83 2.88 2.91
Declared Refrigerant Capacity P
B
1,3,5 kW 769.6 / 680.4 783.3 / 694.1 806.4 / 708.1
Declared Power Input D
B
kW 195.8 / 169.3 197.0 / 170.5 199.9 / 172.6
Declared EER
DC,B
3.93 / 4.02 3.98 / 4.07 4.03 / 4.10
Declared Refrigerant Capacity P
C
1,3,5 kW 741.6 / 641.4 754.6 / 654.6 769.6 / 669.5
Declared Power Input D
C
kW 141.9 / 119.4 142.6 / 120.1 144.3 / 121.8
Declared EER
DC,C
5.23 / 5.37 5.29 / 5.45 5.33 / 5.50
Declared Refrigerant Capacity P
D
1,3,5 kW 602.2 / 558.4 620.5 / 562.6 637.1 / 576.4
Declared Power Input D
D
kW 62.4 / 86.5 63.3 / 86.8 64.9 / 88.7
Declared EER
DC,D
9.65 / 6.46 9.80 / 6.48 9.82 / 6.49
SSCEE
2,3,5 % 0.2 163.3 163.9
SSCEE Tier
6 Not Compliant Tier 1 (2018) Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5 n/a 786.1 807.4
Declared Cooling Capacity 35°C Pdc
2,3,5 kW n/a 781.4 802.5
Declared EER
d
35°C
n/a 2.88 2.91
Declared Cooling Capacity 30°C Pdc
2,3,5 kW n/a 783.3 / 694.1 806.4 / 708.1
Declared EER
d
30°C
n/a 3.98 / 4.07 4.03 / 4.10
Declared Cooling Capacity 25°C Pdc
2,3,5 kW n/a 754.6 / 654.6 769.6 / 669.5
Declared EER
d
25°C
n/a 5.29 / 5.45 5.33 / 5.50
Declared Cooling Capacity 20°C Pdc
2,3,5 kW n/a 620.5 / 562.6 637.1 / 576.4
Declared EER
d
20°C
n/a 9.80 / 6.48 9.82 / 6.49
Sound Power Level LWA
dB(A) n/a
Air ow rate
m³/h n/a 273432 287823
Off mode P
OFF
kW n/a 0.169 0.169
Thermostat-off mode P
TO
kW n/a 5.359 5.614
Standby Mode P
SB
kW n/a 0.373 0.378
Crankcase heater mode P
CK
kW n/a 0.000 0.000
Technical Data
Ecodesign
DCF082TX-18GYYY, DCF085TX-19HYYV, DCF088TX-20HYVV
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside conguration.
(6)
Please contact Airedale regarding Non Compliant selections