Notes: Units DCF099TX-21HWWW DCF050DX-13DXY0 DCF053DX-13DPY0
SEPR
1,3,5 6.46 6.81 6.72
SEPR Tier
Tier 2 (2021) Tier 2 (2021) Tier 2 (2021)
Annual Electricity Consumption
kWh/a 1046771 504988 529282
Rated Refrigerant Capacity
P
A
1,3,5 kW 913 464.1 480.1
Rated Power Input D
A
kW 323.8 151.7 156.9
Rated EER
DC,A
2.82 3.06 3.06
Declared Refrigerant Capacity P
B
1,3,5 kW 926.4 / 819.7 522.5 / 429.3 541.0 / 446.8
Declared Power Input D
B
kW 234.6 / 202.6 125.8 / 100.3 130.0 / 104.3
Declared EER
DC,B
3.95 / 4.05 4.15 / 4.28 4.16 / 4.28
Declared Refrigerant Capacity P
C
1,3,5 kW 891.6 / 771.4 466.6 / 385.7 486.4 / 379.7
Declared Power Input D
C
kW 169.1 / 142.1 83.7 / 67.5 87.5 / 67.7
Declared EER
DC,C
5.27 / 5.43 5.57 / 5.71 5.56 / 5.61
Declared Refrigerant Capacity P
D
1,3,5 kW 725.6 / 670.6 368.6 / 287.7 380.8 / 253.5
Declared Power Input D
D
kW 74.1 / 102.2 35.9 / 42.9 37.8 / 38.9
Declared EER
DC,D
9.79 / 6.56 10.26 / 6.70 10.06 / 6.52
SSCEE
2,3,5 % 164.7 172.3 167.0
SSCEE Tier
6 Tier 1 (2018) Tier 1 (2018) Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5 917.9 466.7 483.4
Declared Cooling Capacity 35°C Pdc
2,3,5 kW 913 464.1 480.1
Declared EER
d
35°C
2.82 3.06 3.06
Declared Cooling Capacity 30°C Pdc
2,3,5 kW 926.4 / 819.7 522.5 / 429.3 541.0 / 446.8
Declared EER
d
30°C
3.95 / 4.05 4.15 / 4.28 4.16 / 4.28
Declared Cooling Capacity 25°C Pdc
2,3,5 kW 891.6 / 771.4 466.6 / 385.7 486.4 / 379.7
Declared EER
d
25°C
5.27 / 5.43 5.57 / 5.71 5.56 / 5.61
Declared Cooling Capacity 20°C Pdc
2,3,5 kW 725.6 / 670.6 368.6 / 287.7 380.8 / 253.5
Declared EER
d
20°C
9.79 / 6.56 10.26 / 6.70 10.06 / 6.52
Sound Power Level LWA
dB(A)
Air ow rate
m³/h 302214 187085 187085
Off mode P
OFF
kW 0.169 0.157 0.157
Thermostat-off mode P
TO
kW 5.755 3.045 3.741
Standby Mode P
SB
kW 0.383 0.296 0.284
Crankcase heater mode P
CK
kW 0.000 0.000 0.000
Technical Data
Ecodesign
DCF099TX-21HWWW, DCF050DX-13DXY0, DCF053DX-13DPY0
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside conguration.
(6)
Please contact Airedale regarding Non Compliant selections