Technical Data
Ecodesign
DCC077TX-16GYYV, DCC080TX-17GYVV, DCC083TX-18GVVV
Notes: Units DCC077TX-16GYYV DCC080TX-17GYVV DCC083TX-18GVVV
SEPR
1,3,5 5.50 5.56 5.61
SEPR Tier
Tier 1 (2018) Tier 2 (2021) Tier 2 (2021)
Annual Electricity Consumption
kWh/a 1020572 1039649 1058596
Rated Refrigerant Capacity
P
A
1,3,5 kW 757.4 779.7 801.7
Rated Power Input D
A
kW 273.4 276.5 279.3
Rated EER
DC,A
2.77 2.82 2.87
Declared Refrigerant Capacity P
B
1,3,5 kW 762.7 / 678.4 787.0 / 692.8 811.0 / 716.8
Declared Power Input D
B
kW 197.3 / 170.0 199.1 / 171.6 201.3 / 173.8
Declared EER
DC,B
3.87 / 3.99 3.95 / 4.04 4.03 / 4.13
Declared Refrigerant Capacity P
C
1,3,5 kW 736.8 / 641.1 752.3 / 656.5 777.1 / 671.7
Declared Power Input D
C
kW 141.9 / 119.0 143.0 / 120.1 144.9 / 121.6
Declared EER
DC,C
5.19 / 5.39 5.26 / 5.47 5.36 / 5.53
Declared Refrigerant Capacity P
D
1,3,5 kW 671.5 / 554.6 685.3 / 568.3 698.7 / 581.8
Declared Power Input D
D
kW 102.2 / 84.9 103.7 / 86.4 105.5 / 88.3
Declared EER
DC,D
6.57 / 6.53 6.61 / 6.58 6.62 / 6.59
SSCEE
2,3,5 % 167.1 169.8 171.6
SSCEE Tier
6 Tier 1 (2018) Tier 1 (2018) Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5 760.2 782.4 804.7
Declared Cooling Capacity 35°C Pdc
2,3,5 kW 757.4 779.7 801.7
Declared EER
d
35°C
2.77 2.82 2.87
Declared Cooling Capacity 30°C Pdc
2,3,5 kW 762.7 / 678.4 787.0 / 692.8 811.0 / 716.8
Declared EER
d
30°C
3.87 / 3.99 3.95 / 4.04 4.03 / 4.13
Declared Cooling Capacity 25°C Pdc
2,3,5 kW 736.8 / 641.1 752.3 / 656.5 777.1 / 671.7
Declared EER
d
25°C
5.19 / 5.39 5.26 / 5.47 5.36 / 5.53
Declared Cooling Capacity 20°C Pdc
2,3,5 kW 671.5 / 554.6 685.3 / 568.3 698.7 / 581.8
Declared EER
d
20°C
6.57 / 6.53 6.61 / 6.58 6.62 / 6.59
Sound Power Level LWA
dB(A) 89 89 90
Air ow rate
m³/h 254286 270179 286072
Off mode P
OFF
kW 0.169 0.169 0.169
Thermostat-off mode P
TO
kW 3.847 3.324 3.555
Standby Mode P
SB
kW 0.358 0.363 0.368
Crankcase heater mode P
CK
kW 0.000 0.000 0.000
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside conguration.
(6)
Please contact Airedale regarding Non Compliant selections