Technical Data
Ecodesign
DCF085TR-14HYVV, DCF090TR-15HVVV, DCF092TR-15HVVW
Notes: Units DCF085TR-14HYVV DCF090TR-15HVVV DCF092TR-15HVVW
SEPR
1,3,5 5.57 5.81 5.77
SEPR Tier
Tier 2 (2021) Tier 2 (2021) Tier 2 (2021)
Annual Electricity Consumption
kWh/a 1051131 1053667 1095429
Rated Refrigerant Capacity
P
A
1,3,5 kW 789.8 826 853.3
Rated Power Input D
A
kW 296.9 301.5 316.0
Rated EER
DC,A
2.66 2.74 2.7
Declared Refrigerant Capacity P
B
1,3,5 kW 789.6 / 692.5 827.6 / 729.0 851.3 / 752.6
Declared Power Input D
B
kW 215.7 / 185.4 219.0 / 188.6 226.7 / 196.3
Declared EER
DC,B
3.66 / 3.73 3.78 / 3.87 3.76 / 3.83
Declared Refrigerant Capacity P
C
1,3,5 kW 749.5 / 653.9 790.2 / 683.8 815.3 / 708.8
Declared Power Input D
C
kW 155.6 / 130.1 158.1 / 132.5 164.5 / 138.8
Declared EER
DC,C
4.82 / 5.02 5.00 / 5.16 4.96 / 5.11
Declared Refrigerant Capacity P
D
1,3,5 kW 626.3 / 573.7 654.7 / 604.6 676.9 / 618.8
Declared Power Input D
D
kW 82.9 / 92.5 81.7 / 94.5 84.5 / 96.3
Declared EER
DC,D
7.55 / 6.20 8.02 / 6.40 8.01 / 6.42
SSCEE
2,3,5 % 151.2 154.5 155.0
SSCEE Tier
6 Not Compliant Not Compliant Not Compliant
Rated Cooling Capacity P
rated,c
2,4,5 n/a n/a n/a
Declared Cooling Capacity 35°C Pdc
2,3,5 kW n/a n/a n/a
Declared EER
d
35°C
n/a n/a n/a
Declared Cooling Capacity 30°C Pdc
2,3,5 kW n/a n/a n/a
Declared EER
d
30°C
n/a n/a n/a
Declared Cooling Capacity 25°C Pdc
2,3,5 kW n/a n/a n/a
Declared EER
d
25°C
n/a n/a n/a
Declared Cooling Capacity 20°C Pdc
2,3,5 kW n/a n/a n/a
Declared EER
d
20°C
n/a n/a n/a
Sound Power Level LWA
dB(A) n/a n/a n/a
Air ow rate
m³/h n/a n/a n/a
Off mode P
OFF
kW n/a n/a n/a
Thermostat-off mode P
TO
kW n/a n/a n/a
Standby Mode P
SB
kW n/a n/a n/a
Crankcase heater mode P
CK
kW n/a n/a n/a
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside conguration.
(6)
Please contact Airedale regarding Non Compliant selections