Technical Data
Ecodesign
DCC059DR-14DVV0, DCC061DR-14DVW0, DCC065DR-14DWW0
Notes: Units DCC059DR-14DVV0 DCC061DR-14DVW0 DCC065DR-14DWW0
SEPR
1,3,5 5.78 5.70 5.60
SEPR Tier
Tier 2 (2021) Tier 2 (2021) Tier 2 (2021)
Annual Electricity Consumption
kWh/a 727164 773760 837292
Rated Refrigerant Capacity
P
A
1,3,5 kW 567.6 595.5 633.1
Rated Power Input D
A
kW 182.5 196.5 211.7
Rated EER
DC,A
3.11 3.03 2.99
Declared Refrigerant Capacity P
B
1,3,5 kW 630.0 / 528.1 660.3 / 548.5 702.8 / 589.5
Declared Power Input D
B
kW 149.9 / 123.0 161.0 / 129.7 174.5 / 143.1
Declared EER
DC,B
4.20 / 4.29 4.10 / 4.23 4.03 / 4.12
Declared Refrigerant Capacity P
C
1,3,5 kW 569.7 / 460.2 590.9 / 482.1 635.7 / 514.0
Declared Power Input D
C
kW 102.6 / 80.1 108.1 / 85.6 119.7 / 93.2
Declared EER
DC,C
5.55 / 5.75 5.47 / 5.63 5.31 / 5.52
Declared Refrigerant Capacity P
D
1,3,5 kW 475.7 / 356.1 499.1 / 367.3 534.8 / 400.3
Declared Power Input D
D
kW 70.8 / 53.6 74.9 / 55.4 81.0 / 61.4
Declared EER
DC,D
6.72 / 6.65 6.67 / 6.63 6.61 / 6.52
SSCEE
2,3,5 % 176.2 175.8 168.1
SSCEE Tier
6 Tier 1 (2018) Tier 1 (2018) Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5 570 597.7 636.5
Declared Cooling Capacity 35°C Pdc
2,3,5 kW 567.6 595.5 633.1
Declared EER
d
35°C
3.11 3.03 2.99
Declared Cooling Capacity 30°C Pdc
2,3,5 kW 630.0 / 528.1 660.3 / 548.5 702.8 / 589.5
Declared EER
d
30°C
4.20 / 4.29 4.10 / 4.23 4.03 / 4.12
Declared Cooling Capacity 25°C Pdc
2,3,5 kW 569.7 / 460.2 590.9 / 482.1 635.7 / 514.0
Declared EER
d
25°C
5.55 / 5.75 5.47 / 5.63 5.31 / 5.52
Declared Cooling Capacity 20°C Pdc
2,3,5 kW 475.7 / 356.1 499.1 / 367.3 534.8 / 400.3
Declared EER
d
20°C
6.72 / 6.65 6.67 / 6.63 6.61 / 6.52
Sound Power Level LWA
dB(A) 91 92 93
Air ow rate
m³/h 324791 324791 324791
Off mode P
OFF
kW 0.157 0.157 0.157
Thermostat-off mode P
TO
kW 2.909 2.677 4.074
Standby Mode P
SB
kW 0.301 0.301 0.301
Crankcase heater mode P
CK
kW 0.000 0.000 0.000
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside conguration.
(6)
Please contact Airedale regarding Non Compliant selections