Technical Data
Ecodesign
DCC088TX-21GVVW, DCC091TX-21GVWW, DCC094TX-21GWWW
Notes: Units DCC088TX-21GVVW DCC091TX-21GVWW DCC094TX-21GWWW
SEPR
1,3,5 5.79 5.73 5.66
SEPR Tier
Tier 2 (2021) Tier 2 (2021) Tier 2 (2021)
Annual Electricity Consumption
kWh/a 1098674 1146420 1196639
Rated Refrigerant Capacity
P
A
1,3,5 kW 858.3 886 913.7
Rated Power Input D
A
kW 285.1 299.3 314.0
Rated EER
DC,A
3.01 2.96 2.91
Declared Refrigerant Capacity P
B
1,3,5 kW 858.7 / 759.2 890.4 / 782.8 922.0 / 814.4
Declared Power Input D
B
kW 203.1 / 176.6 214.9 / 183.9 226.7 / 195.8
Declared EER
DC,B
4.23 / 4.30 4.14 / 4.26 4.07 / 4.16
Declared Refrigerant Capacity P
C
1,3,5 kW 822.2 / 713.4 846.9 / 738.1 882.9 / 762.8
Declared Power Input D
C
kW 147.2 / 124.7 153.3 / 130.8 163.3 / 136.9
Declared EER
DC,C
5.59 / 5.72 5.52 / 5.64 5.41 / 5.57
Declared Refrigerant Capacity P
D
1,3,5 kW 739.2 / 606.5 766.0 / 633.3 792.9 / 660.2
Declared Power Input D
D
kW 109.4 / 89.9 114.1 / 94.6 118.8 / 99.3
Declared EER
DC,D
6.76 / 6.75 6.72 / 6.70 6.68 / 6.65
SSCEE
2,3,5 % 179.3 177.0 174.1
SSCEE Tier
6 Tier 2 (2021) Tier 1 (2018) Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5 860.8 888.7 916.6
Declared Cooling Capacity 35°C Pdc
2,3,5 kW 858.3 886 913.7
Declared EER
d
35°C
3.01 2.96 2.91
Declared Cooling Capacity 30°C Pdc
2,3,5 kW 858.7 / 759.2 890.4 / 782.8 922.0 / 814.4
Declared EER
d
30°C
4.23 / 4.30 4.14 / 4.26 4.07 / 4.16
Declared Cooling Capacity 25°C Pdc
2,3,5 kW 822.2 / 713.4 846.9 / 738.1 882.9 / 762.8
Declared EER
d
25°C
5.59 / 5.72 5.52 / 5.64 5.41 / 5.57
Declared Cooling Capacity 20°C Pdc
2,3,5 kW 739.2 / 606.5 766.0 / 633.3 792.9 / 660.2
Declared EER
d
20°C
6.76 / 6.75 6.72 / 6.70 6.68 / 6.65
Sound Power Level LWA
dB(A) 90 91 91
Air ow rate
m³/h 333751 333751 333751
Off mode P
OFF
kW 0.169 0.169 0.169
Thermostat-off mode P
TO
kW 3.145 3.398 3.663
Standby Mode P
SB
kW 0.383 0.383 0.383
Crankcase heater mode P
CK
kW 0.000 0.000 0.000
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside conguration.
(6)
Please contact Airedale regarding Non Compliant selections