ELECTRICAL DATA 52 53 54
Unit Data DCF047DX-09DXY0 DCF049DX-09DPY0 DCF051DX-10DPV0
Nominal Run Amps (1) A 300.7 311.1 339.4
Maximum Start Amps A 576.3 574.5 602.8
Recommended Mains Fuse Size A 315 355 400
Evaporator
Immersion Heater Rating W 170 170 170
Condenser Fan - Per Fan (EC)
Quantity 9 9 10
Full Load Amps A 3.9 3.9 3.9
Motor Rating kW 2.6 2.6 2.6
Compressor - Per Compressor
Nominal Run Amps A 36 / 47.9 59.2 / 47.9 59.2 / 55.2
Quantity 3 + 3 2 + 3 2 + 3
Motor Rating kW 22.7 / 29.8 36.2 / 29.8 36.2 / 33.1
Sump Heater Rating W 140 140 140
Start Amps (2) A 210 / 326 298 / 326 298 / 326
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98) (3)
Nominal Run Amps A 288.9 295.0 316.2
Reactive power reduction/saving (4) kVAr 22.6 29.9 41.1
Maximum Start Amps A 564.5 558.4 579.6
Recommended Mains Fuse Size A 315 355 400
Electronic Soft-start
Nominal Run Amps A 300.7 311.1 339.4
Maximum Start Amps A 445.9 444.1 472.4
Recommended Mains Fuse A 315 355 400
Power Factor Correction (PF
0.98) & Electronic Soft Start (3)
Nominal Run Amps A 288.9 295.0 316.2
Maximum Start Amps A 434.1 428.0 449.2
Recommended Mains Fuse Size A 315 355 400
Standard Head Pump (Single
or Run/Standby)
Pump Full Load Amps A 14.8 14.8 14.8
Unit Nominal Run Amps A 315.2 325.7 354.1
Recommended Mains Fuse Size A 355 355 400
Motor Rating kW 8.4 8.4 8.4
Larger Head Pump (Single
or Run/Standby)
Pump Full Load Amps A 21.2 21.2 21.2
Unit Nominal Run Amps A 321.6 332.1 360.5
Recommended Mains Fuse Size A 355 355 400
Motor Rating kW 12.1 12.1 12.1
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps A 13.9 13.9 13.9
Unit Nominal Run Amps A 312.1 322.4 350.5
Recommended Mains Fuse Size A 355 355 400
Motor Rating kW 8.6 8.6 8.6
Larger Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps A 19.8 19.8 19.8
Unit Nominal Run Amps A 317.1 327.3 355.3
Recommended Mains Fuse Size A 355 355 400
Motor Rating kW 12.4 12.4 12.4
DCF Electrical Data Extra Quiet
(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.