Technical Data
Ecodesign
DCC050DR-12EPV0, DCC052DR-12EYY0, DCC056DR-13DYV0
Notes: Units DCC050DR-12EPV0 DCC052DR-12EYY0 DCC056DR-13DYV0
SEPR
1,3,5 5.62 5.47 5.70
SEPR Tier
Tier 2 (2021) Tier 1 (2018) Tier 2 (2021)
Annual Electricity Consumption
kWh/a 643239 690785 703938
Rated Refrigerant Capacity
P
A
1,3,5 kW 487.5 509.6 541.5
Rated Power Input D
A
kW 160.4 173.3 177.5
Rated EER
DC,A
3.04 2.94 3.05
Declared Refrigerant Capacity P
B
1,3,5 kW 539.9 / 442.0 563.9 / 472.9 600.2 / 499.7
Declared Power Input D
B
kW 131.4 / 104.9 143.0 / 117.2 145.9 / 119.2
Declared EER
DC,B
4.11 / 4.21 3.94 / 4.04 4.11 / 4.19
Declared Refrigerant Capacity P
C
1,3,5 kW 475.9 / 368.3 508.0 / 410.5 538.1 / 438.1
Declared Power Input D
C
kW 87.3 / 67.0 97.7 / 75.9 99.3 / 77.4
Declared EER
DC,C
5.45 / 5.50 5.20 / 5.41 5.42 / 5.66
Declared Refrigerant Capacity P
D
1,3,5 kW 497.3 / 384.6 424.6 / 317.9 453.3 / 336.2
Declared Power Input D
D
kW 75.7 / 58.8 66.3 / 50.1 67.9 / 50.8
Declared EER
DC,D
6.57 / 6.54 6.41 / 6.34 6.68 / 6.62
SSCEE
2,3,5 % 17%.6 167.9 176.6
SSCEE Tier
6 Tier 1 (2018) Tier 1 (2018) Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5 489.5 511.8 543.1
Declared Cooling Capacity 35°C Pdc
2,3,5 kW 487.5 509.6 541.5
Declared EER
d
35°C
3.04 2.94 3.05
Declared Cooling Capacity 30°C Pdc
2,3,5 kW 539.9 / 442.0 563.9 / 472.9 600.2 / 499.7
Declared EER
d
30°C
4.11 / 4.21 3.94 / 4.04 4.11 / 4.19
Declared Cooling Capacity 25°C Pdc
2,3,5 kW 475.9 / 368.3 508.0 / 410.5 538.1 / 438.1
Declared EER
d
25°C
5.45 / 5.50 5.20 / 5.41 5.42 / 5.66
Declared Cooling Capacity 20°C Pdc
2,3,5 kW 497.3 / 384.6 424.6 / 317.9 453.3 / 336.2
Declared EER
d
20°C
6.57 / 6.54 6.41 / 6.34 6.68 / 6.62
Sound Power Level LWA
dB(A) 91 91 91
Air ow rate
m³/h 278393 278393 301592
Off mode P
OFF
kW 0.157 0.157 0.157
Thermostat-off mode P
TO
kW 2.312 2.574 2.008
Standby Mode P
SB
kW 0.279 0.291 0.296
Crankcase heater mode P
CK
kW 0.000 0.000 0.000
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside conguration.
(6)
Please contact Airedale regarding Non Compliant selections