Technical Data
Ecodesign
DCC058DR-12DVV0, DCC060DR-12DVW0, DCC063DR-12DWW0
Notes: Units DCC058DR-12DVV0 DCC060DR-12DVW0 DCC063DR-12DWW0
SEPR
1,3,5 5.66 5.57 5.47
SEPR Tier
Tier 2 (2021) Tier 2 (2021) Tier 1 (2018)
Annual Electricity Consumption
kWh/a 734089 782645 848411
Rated Refrigerant Capacity
P
A
1,3,5 kW 560.9 588.8 626.1
Rated Power Input D
A
kW 187.6 201.6 218.2
Rated EER
DC,A
2.99 2.92 2.87
Declared Refrigerant Capacity P
B
1,3,5 kW 623.0 / 522.8 652.8 / 543.0 694.2 / 583.0
Declared Power Input D
B
kW 154.1 / 126.2 165.7 / 133.2 179.7 / 147.0
Declared EER
DC,B
4.04 / 4.14 3.94 / 4.08 3.86 / 3.97
Declared Refrigerant Capacity P
C
1,3,5 kW 564.0 / 456.3 585.0 / 477.9 628.9 / 509.3
Declared Power Input D
C
kW 105.4 / 81.9 111.1 / 87.6 123.1 / 95.5
Declared EER
DC,C
5.35 / 5.57 5.27 / 5.45 5.11 / 5.33
Declared Refrigerant Capacity P
D
1,3,5 kW 475.7 / 356.2 499.1 / 367.3 534.9 / 400.4
Declared Power Input D
D
kW 71.1 / 53.7 75.3 / 55.6 81.6 / 61.7
Declared EER
DC,D
6.69 / 6.63 6.63 / 6.61 6.56 / 6.49
SSCEE
2,3,5 % 172.3 171.8 164.3
SSCEE Tier
6 Tier 1 (2018) Tier 1 (2018) Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5 563.2 590.9 629.4
Declared Cooling Capacity 35°C Pdc
2,3,5 kW 560.9 588.8 626.1
Declared EER
d
35°C
2.99 2.92 2.87
Declared Cooling Capacity 30°C Pdc
2,3,5 kW 623.0 / 522.8 652.8 / 543.0 694.2 / 583.0
Declared EER
d
30°C
4.04 / 4.14 3.94 / 4.08 3.86 / 3.97
Declared Cooling Capacity 25°C Pdc
2,3,5 kW 564.0 / 456.3 585.0 / 477.9 628.9 / 509.3
Declared EER
d
25°C
5.35 / 5.57 5.27 / 5.45 5.11 / 5.33
Declared Cooling Capacity 20°C Pdc
2,3,5 kW 475.7 / 356.2 499.1 / 367.3 534.9 / 400.4
Declared EER
d
20°C
6.69 / 6.63 6.63 / 6.61 6.56 / 6.49
Sound Power Level LWA
dB(A) 92 93 94
Air ow rate
m³/h 278393 278393 278393
Off mode P
OFF
kW 0.157 0.157 0.157
Thermostat-off mode P
TO
kW 2.807 2.581 3.930
Standby Mode P
SB
kW 0.291 0.291 0.291
Crankcase heater mode P
CK
kW 0.000 0.000 0.000
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside conguration.
(6)
Please contact Airedale regarding Non Compliant selections