Technical Data
Ecodesign
DCC086TR-15GVVW, DCC088TR-15GVWW, DCC091TR-15GWWW
Notes: Units DCC086TR-15GVVW DCC088TR-15GVWW DCC091TR-15GWWW
SEPR
1,3,5 5.47 5.39 5.31
SEPR Tier
Tier 1 (2018) Tier 1 (2018) Tier 1 (2018)
Annual Electricity Consumption
kWh/a 1150226 1204063 1260607
Rated Refrigerant Capacity
P
A
1,3,5 kW 849.2 876.4 903.5
Rated Power Input D
A
kW 304.4 318.7 333.4
Rated EER
DC,A
2.79 2.75 2.71
Declared Refrigerant Capacity P
B
1,3,5 kW 841.3 / 743.9 874.5 / 766.6 907.6 / 799.7
Declared Power Input D
B
kW 216.7 / 187.4 229.7 / 195.3 242.7 / 208.3
Declared EER
DC,B
3.88 / 3.97 3.81 / 3.92 3.74 / 3.84
Declared Refrigerant Capacity P
C
1,3,5 kW 803.3 / 698.6 827.3 / 722.6 861.6 / 746.6
Declared Power Input D
C
kW 156.6 / 131.8 163.2 / 138.5 174.2 / 145.2
Declared EER
DC,C
5.13 / 5.30 5.07 / 5.22 4.95 / 5.14
Declared Refrigerant Capacity P
D
1,3,5 kW 739.0 / 606.8 765.5 / 633.2 791.9 / 659.7
Declared Power Input D
D
kW 112.1 / 91.1 117.6 / 96.6 123.1 / 102.1
Declared EER
DC,D
6.60 / 6.66 6.51 / 6.55 6.44 / 6.46
SSCEE
2,3,5 % 169.5 167.3 164.4
SSCEE Tier
6 Tier 1 (2018) Tier 1 (2018) Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5 851.5 878.9 906.2
Declared Cooling Capacity 35°C Pdc
2,3,5 kW 849.2 876.4 903.5
Declared EER
d
35°C
2.79 2.75 2.71
Declared Cooling Capacity 30°C Pdc
2,3,5 kW 841.3 / 743.9 874.5 / 766.6 907.6 / 799.7
Declared EER
d
30°C
3.88 / 3.97 3.81 / 3.92 3.74 / 3.84
Declared Cooling Capacity 25°C Pdc
2,3,5 kW 803.3 / 698.6 827.3 / 722.6 861.6 / 746.6
Declared EER
d
25°C
5.13 / 5.30 5.07 / 5.22 4.95 / 5.14
Declared Cooling Capacity 20°C Pdc
2,3,5 kW 739.0 / 606.8 765.5 / 633.2 791.9 / 659.7
Declared EER
d
20°C
6.60 / 6.66 6.51 / 6.55 6.44 / 6.46
Sound Power Level LWA
dB(A) 95 95 96
Air ow rate
m³/h 347991 347991 347991
Off mode P
OFF
kW 0.169 0.169 0.169
Thermostat-off mode P
TO
kW 2.970 3.206 3.453
Standby Mode P
SB
kW 0.353 0.353 0.353
Crankcase heater mode P
CK
kW 0.000 0.000 0.000
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside conguration.
(6)
Please contact Airedale regarding Non Compliant selections