Technical Data
Ecodesign
DCC079TX-21GYYY, DCC081TX-22GYYV
Notes: Units DCC079TX-21GYYY DCC081TX-22GYYV
SEPR
1,3,5 5.74 5.76
SEPR Tier
Tier 2 (2021) Tier 2 (2021)
Annual Electricity Consumption
kWh/a 1005705 1027664
Rated Refrigerant Capacity
P
A
1,3,5 kW 779.1 798.7
Rated Power Input D
A
kW 253.0 256.8
Rated EER
DC,A
3.08 3.11
Declared Refrigerant Capacity P
B
1,3,5 kW 778.4 / 684.8 791.9 / 698.4
Declared Power Input D
B
kW 184.1 / 159.2 186.3 / 161.4
Declared EER
DC,B
4.23 / 4.30 4.25 / 4.33
Declared Refrigerant Capacity P
C
1,3,5 kW 739.5 / 638.4 753.9 / 652.8
Declared Power Input D
C
kW 132.7 / 111.7 134.4 / 113.4
Declared EER
DC,C
5.57 / 5.72 5.61 / 5.76
Declared Refrigerant Capacity P
D
1,3,5 kW 657.9 / 547.7 671.4 / 554.4
Declared Power Input D
D
kW 99.0 / 82.9 101.0 / 84.0
Declared EER
DC,D
6.64 / 6.60 6.64 / 6.60
SSCEE
2,3,5 % 176.5 176.7
SSCEE Tier
6 Tier 1 (2018) Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5 781.8 801.7
Declared Cooling Capacity 35°C Pdc
2,3,5 kW 779.1 798.7
Declared EER
d
35°C
3.08 3.11
Declared Cooling Capacity 30°C Pdc
2,3,5 kW 778.4 / 684.8 791.9 / 698.4
Declared EER
d
30°C
4.23 / 4.30 4.25 / 4.33
Declared Cooling Capacity 25°C Pdc
2,3,5 kW 739.5 / 638.4 753.9 / 652.8
Declared EER
d
25°C
5.57 / 5.72 5.61 / 5.76
Declared Cooling Capacity 20°C Pdc
2,3,5 kW 657.9 / 547.7 671.4 / 554.4
Declared EER
d
20°C
6.64 / 6.60 6.64 / 6.60
Sound Power Level LWA
dB(A) 88 89
Air ow rate
m³/h 333751 349644
Off mode P
OFF
kW 0.169 0.169
Thermostat-off mode P
TO
kW 3.370 3.580
Standby Mode P
SB
kW 0.383 0.388
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside conguration.
(6)
Please contact Airedale regarding Non Compliant selections
Chillers
Introduction
DeltaChill™ Air Cooled and FreeCool
266
Chiller Technical Manual 7267818 V1.13.0_01_2018