Technical Data
Ecodesign
DCF053DR-08DYY0, DCF055DR-09DYV0, DCF058DR-10DVV0
Notes: Units DCF053DR-08DYY0 DCF055DR-09DYV0 DCF058DR-10DVV0
SEPR
1,3,5 5.59 5.67 5.95
SEPR Tier
Tier 2 (2021) Tier 2 (2021) Tier 2 (2021)
Annual Electricity Consumption
kWh/a 652445 675330 675955
Rated Refrigerant Capacity
P
A
1,3,5 kW 492.2 517 542.5
Rated Power Input D
A
kW 193.0 196.6 199.4
Rated EER
DC,A
2.55 2.63 2.72
Declared Refrigerant Capacity P
B
1,3,5 kW 470.2 / 382.2 485.6 / 397.6 510.6 / 413.6
Declared Power Input D
B
kW 131.8 / 101.9 133.3 / 103.4 134.5 / 104.2
Declared EER
DC,B
3.57 / 3.75 3.64 / 3.84 3.80 / 3.97
Declared Refrigerant Capacity P
C
1,3,5 kW 510.1 / 414.6 526.8 / 431.2 553.2 / 448.6
Declared Power Input D
C
kW 111.1 / 85.6 112.2 / 86.7 112.5 / 87.1
Declared EER
DC,C
4.59 / 4.84 4.70 / 4.97 4.92 / 5.15
Declared Refrigerant Capacity P
D
1,3,5 kW 390.1 / 331.5 409.8 / 338.7 430.6 / 356.2
Declared Power Input D
D
kW 48.6 / 54.5 50.9 / 55.6 50.2 / 55.7
Declared EER
DC,D
8.03 / 6.08 8.05 / 6.09 8.58 / 6.39
SSCEE
2,3,5 % 148.8 15%.5 157.8
SSCEE Tier
6 Not Compliant Not Compliant Not Compliant
Rated Cooling Capacity P
rated,c
2,4,5 n/a n/a n/a
Declared Cooling Capacity 35°C Pdc
2,3,5 kW n/a n/a n/a
Declared EER
d
35°C
n/a n/a n/a
Declared Cooling Capacity 30°C Pdc
2,3,5 kW n/a n/a n/a
Declared EER
d
30°C
n/a n/a n/a
Declared Cooling Capacity 25°C Pdc
2,3,5 kW n/a n/a n/a
Declared EER
d
25°C
n/a n/a n/a
Declared Cooling Capacity 20°C Pdc
2,3,5 kW n/a n/a n/a
Declared EER
d
20°C
n/a n/a n/a
Sound Power Level LWA
dB(A) n/a n/a n/a
Air ow rate
m³/h n/a n/a n/a
Off mode P
OFF
kW n/a n/a n/a
Thermostat-off mode P
TO
kW n/a n/a n/a
Standby Mode P
SB
kW n/a n/a n/a
Crankcase heater mode P
CK
kW n/a n/a n/a
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside conguration.
(6)
Please contact Airedale regarding Non Compliant selections
Chillers
Introduction
DeltaChill™ Air Cooled and FreeCool
268
Chiller Technical Manual 7267818 V1.13.0_01_2018