Notes: Units DCF053DX-10DYY0 DCF055DX-11DYV0 DCF058DX-12DVV0
SEPR
1,3,5 6.18 6.26 6.42
SEPR Tier
Tier 2 (2021) Tier 2 (2021) Tier 2 (2021)
Annual Electricity Consumption
kWh/a 583618 603072 615152
Rated Refrigerant Capacity
P
A
1,3,5 kW 486.4 509.3 532.9
Rated Power Input D
A
kW 186.4 189.3 192.4
Rated EER
DC,A
2.61 2.69 2.77
Declared Refrigerant Capacity P
B
1,3,5 kW 471.3 / 388.4 486.4 / 403.5 512.2 / 419.2
Declared Power Input D
B
kW 125.7 / 97.4 127.7 / 99.4 129.2 / 100.7
Declared EER
DC,B
3.75 / 3.99 3.81 / 4.06 3.97 / 4.16
Declared Refrigerant Capacity P
C
1,3,5 kW 421.9 / 319.2 532.5 / 437.7 559.8 / 454.2
Declared Power Input D
C
kW 81.6 / 60.3 106.7 / 83.1 107.8 / 83.8
Declared EER
DC,C
5.17 / 5.29 4.99 / 5.27 5.19 / 5.42
Declared Refrigerant Capacity P
D
1,3,5 kW 386.0 / 334.3 404.1 / 341.5 423.5 / 356.6
Declared Power Input D
D
kW 41.0 / 52.3 42.6 / 53.5 43.9 / 54.5
Declared EER
DC,D
9.41 / 6.39 9.50 / 6.39 9.65 / 6.54
SSCEE
2,3,5 % 157.5 158.8 165.4
SSCEE Tier
6 Not Compliant Not Compliant Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5 n/a n/a 535.8
Declared Cooling Capacity 35°C Pdc
2,3,5 kW n/a n/a 532.9
Declared EER
d
35°C
n/a n/a 2.77
Declared Cooling Capacity 30°C Pdc
2,3,5 kW n/a n/a 512.2 / 419.2
Declared EER
d
30°C
n/a n/a 3.97 / 4.16
Declared Cooling Capacity 25°C Pdc
2,3,5 kW n/a n/a 559.8 / 454.2
Declared EER
d
25°C
n/a n/a 5.19 / 5.42
Declared Cooling Capacity 20°C Pdc
2,3,5 kW n/a n/a 423.5 / 356.6
Declared EER
d
20°C
n/a n/a 9.65 / 6.54
Sound Power Level LWA
dB(A) n/a n/a
Air ow rate
m³/h n/a n/a 172694
Off mode P
OFF
kW n/a n/a 0.157
Thermostat-off mode P
TO
kW n/a n/a 3.328
Standby Mode P
SB
kW n/a n/a 0.291
Crankcase heater mode P
CK
kW n/a n/a 0.000
Technical Data
Ecodesign
DCF053DX-10DYY0, DCF055DX-11DYV0, DCF058DX-12DVV0
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside conguration.
(6)
Please contact Airedale regarding Non Compliant selections