Technical Data
Ecodesign
DCC056DX-12DVV0, DCC058DX-12DVW0, DCC061DX-12DWW0
Notes: Units DCC056DX-12DVV0 DCC058DX-12DVW0 DCC061DX-12DWW0
SEPR
1,3,5 5.68 5.60 5.50
SEPR Tier
Tier 2 (2021) Tier 2 (2021) Tier 1 (2018)
Annual Electricity Consumption
kWh/a 708189 749567 805098
Rated Refrigerant Capacity
P
A
1,3,5 kW 543 566.3 597.4
Rated Power Input D
A
kW 187.2 202.3 218.8
Rated EER
DC,A
2.9 2.8 2.73
Declared Refrigerant Capacity P
B
1,3,5 kW 518.2 / 422.7 538.5 / 443.4 575.0 / 472.1
Declared Power Input D
B
kW 125.8 / 98.1 132.7 / 105.1 146.8 / 113.9
Declared EER
DC,B
4.12 / 4.31 4.06 / 4.22 3.92 / 4.14
Declared Refrigerant Capacity P
C
1,3,5 kW 563.6 / 456.5 584.6 / 478.0 626.5 / 509.5
Declared Power Input D
C
kW 105.2 / 81.7 110.8 / 87.4 122.6 / 95.1
Declared EER
DC,C
5.36 / 5.58 5.27 / 5.47 5.11 / 5.36
Declared Refrigerant Capacity P
D
1,3,5 kW 475.9 / 356.3 499.3 / 367.5 535.3 / 400.7
Declared Power Input D
D
kW 70.9 / 53.5 75.2 / 55.4 81.2 / 61.3
Declared EER
DC,D
6.71 / 6.65 6.64 / 6.64 6.59 / 6.54
SSCEE
2,3,5 % 172.9 172.3 165.3
SSCEE Tier
6 Tier 1 (2018) Tier 1 (2018) Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5 545.1 568.2 600.4
Declared Cooling Capacity 35°C Pdc
2,3,5 kW 543 566.3 597.4
Declared EER
d
35°C
2.9 2.8 2.73
Declared Cooling Capacity 30°C Pdc
2,3,5 kW 518.2 / 422.7 538.5 / 443.4 575.0 / 472.1
Declared EER
d
30°C
4.12 / 4.31 4.06 / 4.22 3.92 / 4.14
Declared Cooling Capacity 25°C Pdc
2,3,5 kW 563.6 / 456.5 584.6 / 478.0 626.5 / 509.5
Declared EER
d
25°C
5.36 / 5.58 5.27 / 5.47 5.11 / 5.36
Declared Cooling Capacity 20°C Pdc
2,3,5 kW 475.9 / 356.3 499.3 / 367.5 535.3 / 400.7
Declared EER
d
20°C
6.71 / 6.65 6.64 / 6.64 6.59 / 6.54
Sound Power Level LWA
dB(A) 88 89 89
Air ow rate
m³/h 190715 190715 190715
Off mode P
OFF
kW 0.157 0.157 0.157
Thermostat-off mode P
TO
kW 2.599 2.353 3.505
Standby Mode P
SB
kW 0.291 0.291 0.291
Crankcase heater mode P
CK
kW 0.000 0.000 0.000
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside conguration.
(6)
Please contact Airedale regarding Non Compliant selections