Technical Data
Ecodesign
DCC049DX-12EPV0, DCC051DX-12EYY0, DCC054DX-13DYV0
Notes: Units DCC049DX-12EPV0 DCC051DX-12EYY0 DCC054DX-13DYV0
SEPR
1,3,5 5.62 5.48 5.71
SEPR Tier
Tier 2 (2021) Tier 1 (2018) Tier 2 (2021)
Annual Electricity Consumption
kWh/a 630437 674571 688639
Rated Refrigerant Capacity
P
A
1,3,5 kW 478.3 498.8 530.7
Rated Power Input D
A
kW 159.4 172.6 176.9
Rated EER
DC,A
3 2.89 3
Declared Refrigerant Capacity P
B
1,3,5 kW 536.5 / 439.8 470.4 / 381.9 496.7 / 406.4
Declared Power Input D
B
kW 130.8 / 104.5 116.8 / 91.2 118.8 / 93.1
Declared EER
DC,B
4.10 / 4.21 4.03 / 4.19 4.18 / 4.37
Declared Refrigerant Capacity P
C
1,3,5 kW 476.0 / 368.4 508.1 / 410.6 538.2 / 438.2
Declared Power Input D
C
kW 87.2 / 66.9 97.6 / 75.8 99.3 / 77.3
Declared EER
DC,C
5.46 / 5.51 5.21 / 5.41 5.42 / 5.67
Declared Refrigerant Capacity P
D
1,3,5 kW 384.7 / 247.7 424.7 / 318.0 453.3 / 336.2
Declared Power Input D
D
kW 58.7 / 38.0 66.1 / 50.0 67.8 / 50.7
Declared EER
DC,D
6.56 / 6.51 6.42 / 6.35 6.69 / 6.63
SSCEE
2,3,5 % 17%.3 168.3 176.8
SSCEE Tier
6 Tier 1 (2018) Tier 1 (2018) Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5 480.2 500.9 532.3
Declared Cooling Capacity 35°C Pdc
2,3,5 kW 478.3 498.8 530.7
Declared EER
d
35°C
3 2.89 3
Declared Cooling Capacity 30°C Pdc
2,3,5 kW 536.5 / 439.8 470.4 / 381.9 496.7 / 406.4
Declared EER
d
30°C
4.10 / 4.21 4.03 / 4.19 4.18 / 4.37
Declared Cooling Capacity 25°C Pdc
2,3,5 kW 476.0 / 368.4 508.1 / 410.6 538.2 / 438.2
Declared EER
d
25°C
5.46 / 5.51 5.21 / 5.41 5.42 / 5.67
Declared Cooling Capacity 20°C Pdc
2,3,5 kW 384.7 / 247.7 424.7 / 318.0 453.3 / 336.2
Declared EER
d
20°C
6.56 / 6.51 6.42 / 6.35 6.69 / 6.63
Sound Power Level LWA
dB(A) 88 86 87
Air ow rate
m³/h 190715 190715 206608
Off mode P
OFF
kW 0.157 0.157 0.157
Thermostat-off mode P
TO
kW 2.209 2.444 1.915
Standby Mode P
SB
kW 0.279 0.291 0.296
Crankcase heater mode P
CK
kW 0.000 0.000 0.000
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside conguration.
(6)
Please contact Airedale regarding Non Compliant selections