Notes: Units DCF051DX-11DPY0 DCF053DX-12DPV0 DCF055DX-12DYY0
SEPR
1,3,5 6.49 6.54 6.39
SEPR Tier
Tier 2 (2021) Tier 2 (2021) Tier 2 (2021)
Annual Electricity Consumption
kWh/a 532598 552568 586079
Rated Refrigerant Capacity
P
A
1,3,5 kW 466.4 487.8 505.5
Rated Power Input D
A
kW 161.4 165.4 178.6
Rated EER
DC,A
2.89 2.95 2.83
Declared Refrigerant Capacity P
B
1,3,5 kW 438.9 / 341.7 552.3 / 453.4 482.6 / 393.7
Declared Power Input D
B
kW 107.1 / 82.6 136.6 / 109.3 121.3 / 94.8
Declared EER
DC,B
4.10 / 4.14 4.04 / 4.15 3.98 / 4.15
Declared Refrigerant Capacity P
C
1,3,5 kW 480.2 / 375.0 495.9 / 382.5 527.0 / 427.0
Declared Power Input D
C
kW 90.0 / 69.5 91.8 / 70.6 101.7 / 79.2
Declared EER
DC,C
5.33 / 5.39 5.40 / 5.42 5.18 / 5.39
Declared Refrigerant Capacity P
D
1,3,5 kW 369.8 / 253.5 386.8 / 260.7 401.3 / 334.3
Declared Power Input D
D
kW 37.7 / 38.9 39.1 / 40.1 41.9 / 51.8
Declared EER
DC,D
9.82 / 6.51 9.90 / 6.49 9.57 / 6.46
SSCEE
2,3,5 % 161.0 161.5 163.3
SSCEE Tier
6 Tier 1 (2018) Tier 1 (2018) Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5 469.7 491.4 508.6
Declared Cooling Capacity 35°C Pdc
2,3,5 kW 466.4 487.8 505.5
Declared EER
d
35°C
2.89 2.95 2.83
Declared Cooling Capacity 30°C Pdc
2,3,5 kW 438.9 / 341.7 552.3 / 453.4 482.6 / 393.7
Declared EER
d
30°C
4.10 / 4.14 4.04 / 4.15 3.98 / 4.15
Declared Cooling Capacity 25°C Pdc
2,3,5 kW 480.2 / 375.0 495.9 / 382.5 527.0 / 427.0
Declared EER
d
25°C
5.33 / 5.39 5.40 / 5.42 5.18 / 5.39
Declared Cooling Capacity 20°C Pdc
2,3,5 kW 369.8 / 253.5 386.8 / 260.7 401.3 / 334.3
Declared EER
d
20°C
9.82 / 6.51 9.90 / 6.49 9.57 / 6.46
Sound Power Level LWA
dB(A)
Air ow rate
m³/h 158303 172694 172694
Off mode P
OFF
kW 0.157 0.157 0.157
Thermostat-off mode P
TO
kW 3.678 3.970 3.593
Standby Mode P
SB
kW 0.274 0.279 0.291
Crankcase heater mode P
CK
kW 0.000 0.000 0.000
Technical Data
Ecodesign
DCF051DX-11DPY0, DCF053DX-12DPV0, DCF055DX-12DYY0
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside conguration.
(6)
Please contact Airedale regarding Non Compliant selections