Notes: Units DCF057DX-13DYV0 DCF060DX-14DVV0 DCF064DX-14FVW0
SEPR
1,3,5 6.53 6.60 6.59
SEPR Tier
Tier 2 (2021) Tier 2 (2021) Tier 2 (2021)
Annual Electricity Consumption
kWh/a 597984 615991 660192
Rated Refrigerant Capacity
P
A
1,3,5 kW 527.4 548.7 587.3
Rated Power Input D
A
kW 181.9 186.0 201.8
Rated EER
DC,A
2.9 2.95 2.91
Declared Refrigerant Capacity P
B
1,3,5 kW 497.6 / 408.6 521.2 / 423.0 557.9 / 457.9
Declared Power Input D
B
kW 122.7 / 96.3 125.6 / 98.3 134.5 / 107.0
Declared EER
DC,B
4.05 / 4.25 4.15 / 4.30 4.15 / 4.28
Declared Refrigerant Capacity P
C
1,3,5 kW 543.2 / 443.2 567.6 / 458.8 608.7 / 497.3
Declared Power Input D
C
kW 102.7 / 80.2 105.0 / 81.9 112.7 / 89.4
Declared EER
DC,C
5.29 / 5.52 5.41 / 5.60 5.40 / 5.56
Declared Refrigerant Capacity P
D
1,3,5 kW 419.3 / 342.0 436.1 / 356.6 466.3 / 381.9
Declared Power Input D
D
kW 42.7 / 52.3 44.6 / 54.2 47.5 / 57.5
Declared EER
DC,D
9.82 / 6.54 9.79 / 6.57 9.82 / 6.64
SSCEE
2,3,5 % 168.0 17%.1 168.0
SSCEE Tier
6 Tier 1 (2018) Tier 1 (2018) Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5 530.1 551.6 590.9
Declared Cooling Capacity 35°C Pdc
2,3,5 kW 527.4 548.7 587.3
Declared EER
d
35°C
2.9 2.95 2.91
Declared Cooling Capacity 30°C Pdc
2,3,5 kW 497.6 / 408.6 521.2 / 423.0 557.9 / 457.9
Declared EER
d
30°C
4.05 / 4.25 4.15 / 4.30 4.15 / 4.28
Declared Cooling Capacity 25°C Pdc
2,3,5 kW 543.2 / 443.2 567.6 / 458.8 608.7 / 497.3
Declared EER
d
25°C
5.29 / 5.52 5.41 / 5.60 5.40 / 5.56
Declared Cooling Capacity 20°C Pdc
2,3,5 kW 419.3 / 342.0 436.1 / 356.6 466.3 / 381.9
Declared EER
d
20°C
9.82 / 6.54 9.79 / 6.57 9.82 / 6.64
Sound Power Level LWA
dB(A)
Air ow rate
m³/h 187085 201476 201476
Off mode P
OFF
kW 0.157 0.157 0.157
Thermostat-off mode P
TO
kW 3.144 3.342 4.167
Standby Mode P
SB
kW 0.296 0.301 0.301
Crankcase heater mode P
CK
kW 0.000 0.000 0.000
Technical Data
Ecodesign
DCF057DX-13DYV0, DCF060DX-14DVV0, DCF064DX-14FVW0
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside conguration.
(6)
Please contact Airedale regarding Non Compliant selections