Technical Data
Ecodesign
DCC070TR-16GPPY, DCC074TR-17GPYY, DCC079TR-18GYYY
Notes: Units DCC070TR-16GPPY DCC074TR-17GPYY DCC079TR-18GYYY
SEPR
1,3,5 5.62 5.60 5.62
SEPR Tier
Tier 2 (2021) Tier 2 (2021) Tier 2 (2021)
Annual Electricity Consumption
kWh/a 902454 956222 1026870
Rated Refrigerant Capacity
P
A
1,3,5 kW 685 722.8 778.8
Rated Power Input D
A
kW 226.1 241.7 260.5
Rated EER
DC,A
3.03 2.99 2.99
Declared Refrigerant Capacity P
B
1,3,5 kW 669.4 / 575.2 710.4 / 619.6 771.9 / 679.2
Declared Power Input D
B
kW 160.6 / 136.9 173.4 / 147.6 189.0 / 163.1
Declared EER
DC,B
4.17 / 4.20 4.10 / 4.20 4.08 / 4.16
Declared Refrigerant Capacity P
C
1,3,5 kW 621.3 / 496.0 667.6 / 567.0 732.8 / 633.1
Declared Power Input D
C
kW 114.5 / 88.9 122.9 / 103.1 136.1 / 114.2
Declared EER
DC,C
5.43 / 5.58 5.43 / 5.50 5.38 / 5.55
Declared Refrigerant Capacity P
D
1,3,5 kW 654.3 / 516.8 590.9 / 484.3 658.1 / 547.9
Declared Power Input D
D
kW 99.0 / 78.3 89.9 / 73.8 99.4 / 83.1
Declared EER
DC,D
6.61 / 6.60 6.57 / 6.56 6.62 / 6.59
SSCEE
2,3,5 % 169.1 172.4 172.6
SSCEE Tier
6 Tier 1 (2018) Tier 1 (2018) Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5 688.1 724.9 781.6
Declared Cooling Capacity 35°C Pdc
2,3,5 kW 685 722.8 778.8
Declared EER
d
35°C
3.03 2.99 2.99
Declared Cooling Capacity 30°C Pdc
2,3,5 kW 669.4 / 575.2 710.4 / 619.6 771.9 / 679.2
Declared EER
d
30°C
4.17 / 4.20 4.10 / 4.20 4.08 / 4.16
Declared Cooling Capacity 25°C Pdc
2,3,5 kW 621.3 / 496.0 667.6 / 567.0 732.8 / 633.1
Declared EER
d
25°C
5.43 / 5.58 5.43 / 5.50 5.38 / 5.55
Declared Cooling Capacity 20°C Pdc
2,3,5 kW 654.3 / 516.8 590.9 / 484.3 658.1 / 547.9
Declared EER
d
20°C
6.61 / 6.60 6.57 / 6.56 6.62 / 6.59
Sound Power Level LWA
dB(A) 93 93 93
Air ow rate
m³/h 371190 394390 417589
Off mode P
OFF
kW 0.169 0.169 0.169
Thermostat-off mode P
TO
kW 3.809 2.552 3.315
Standby Mode P
SB
kW 0.335 0.351 0.368
Crankcase heater mode P
CK
kW 0.000 0.000 0.000
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside conguration.
(6)