Notes: Units DCF085TX-17HYVV DCF089TX-18HVVV DCF092TX-18HVVW
SEPR
1,3,5 6.20 6.42 6.38
SEPR Tier
Tier 2 (2021) Tier 2 (2021) Tier 2 (2021)
Annual Electricity Consumption
kWh/a 928723 936291 971522
Rated Refrigerant Capacity
P
A
1,3,5 kW 777.4 811.2 837.2
Rated Power Input D
A
kW 285.8 290.8 305.5
Rated EER
DC,A
2.72 2.79 2.74
Declared Refrigerant Capacity P
B
1,3,5 kW 789.2 / 695.9 827.7 / 733.4 851.2 / 756.9
Declared Power Input D
B
kW 206.6 / 178.1 210.1 / 181.4 217.2 / 188.6
Declared EER
DC,B
3.82 / 3.91 3.94 / 4.04 3.92 / 4.01
Declared Refrigerant Capacity P
C
1,3,5 kW 758.2 / 663.1 799.7 / 692.5 825.3 / 718.2
Declared Power Input D
C
kW 148.7 / 125.0 151.7 / 127.6 157.7 / 133.6
Declared EER
DC,C
5.10 / 5.31 5.27 / 5.43 5.23 / 5.38
Declared Refrigerant Capacity P
D
1,3,5 kW 617.1 / 576.4 643.6 / 605.2 664.7 / 619.5
Declared Power Input D
D
kW 67.3 / 89.5 67.1 / 92.1 69.3 / 94.0
Declared EER
DC,D
9.17 / 6.44 9.59 / 6.57 9.60 / 6.59
SSCEE
2,3,5 % 159.0 161.9 162.5
SSCEE Tier
6 Not Compliant Tier 1 (2018) Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5 n/a 816.6 842.2
Declared Cooling Capacity 35°C Pdc
2,3,5 kW n/a 811.2 837.2
Declared EER
d
35°C
n/a 2.79 2.74
Declared Cooling Capacity 30°C Pdc
2,3,5 kW n/a 827.7 / 733.4 851.2 / 756.9
Declared EER
d
30°C
n/a 3.94 / 4.04 3.92 / 4.01
Declared Cooling Capacity 25°C Pdc
2,3,5 kW n/a 799.7 / 692.5 825.3 / 718.2
Declared EER
d
25°C
n/a 5.27 / 5.43 5.23 / 5.38
Declared Cooling Capacity 20°C Pdc
2,3,5 kW n/a 643.6 / 605.2 664.7 / 619.5
Declared EER
d
20°C
n/a 9.59 / 6.57 9.60 / 6.59
Sound Power Level LWA
dB(A) n/a
Air ow rate
m³/h n/a 259041 259041
Off mode P
OFF
kW n/a 0.169 0.169
Thermostat-off mode P
TO
kW n/a 6.198 5.842
Standby Mode P
SB
kW n/a 0.368 0.368
Crankcase heater mode P
CK
kW n/a 0.000 0.000
Technical Data
Ecodesign
DCF085TX-17HYVV, DCF089TX-18HVVV, DCF092TX-18HVVW
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.