Notes: Units DCF094TR-15HVWW DCF096TR-15HWWW DCF049DR-09DXY0
SEPR
1,3,5 5.70 5.59 6.04
SEPR Tier
Tier 2 (2021) Tier 2 (2021) Tier 2 (2021)
Annual Electricity Consumption
kWh/a 1143043 1194903 558461
Rated Refrigerant Capacity
P
A
1,3,5 kW 879.9 901.6 455.5
Rated Power Input D
A
kW 332.0 345.4 163.3
Rated EER
DC,A
2.65 2.61 2.79
Declared Refrigerant Capacity P
B
1,3,5 kW 884.3 / 775.5 912.5 / 804.2 508.3 / 417.4
Declared Power Input D
B
kW 240.4 / 204.7 252.7 / 217.0 135.2 / 107.1
Declared EER
DC,B
3.68 / 3.79 3.61 / 3.71 3.76 / 3.90
Declared Refrigerant Capacity P
C
1,3,5 kW 839.5 / 733.1 869.7 / 753.4 453.7 / 376.5
Declared Power Input D
C
kW 171.6 / 146.0 181.8 / 151.8 90.0 / 71.9
Declared EER
DC,C
4.89 / 5.02 4.78 / 4.96 5.04 / 5.23
Declared Refrigerant Capacity P
D
1,3,5 kW 697.7 / 644.6 715.7 / 667.1 361.4 / 287.4
Declared Power Input D
D
kW 87.7 / 102.5 92.5 / 107.2 41.6 / 43.9
Declared EER
DC,D
7.96 / 6.29 7.74 / 6.22 8.69 / 6.55
SSCEE
2,3,5 % 152.4 152.1 159.5
SSCEE Tier
6 Not Compliant Not Compliant Not Compliant
Rated Cooling Capacity P
rated,c
2,4,5 n/a n/a n/a
Declared Cooling Capacity 35°C Pdc
2,3,5 kW n/a n/a n/a
Declared EER
d
35°C
n/a n/a n/a
Declared Cooling Capacity 30°C Pdc
2,3,5 kW n/a n/a n/a
Declared EER
d
30°C
n/a n/a n/a
Declared Cooling Capacity 25°C Pdc
2,3,5 kW n/a n/a n/a
Declared EER
d
25°C
n/a n/a n/a
Declared Cooling Capacity 20°C Pdc
2,3,5 kW n/a n/a n/a
Declared EER
d
20°C
n/a n/a n/a
Sound Power Level LWA
dB(A) n/a n/a n/a
Air ow rate
m³/h n/a n/a n/a
Off mode P
OFF
kW n/a n/a n/a
Thermostat-off mode P
TO
kW n/a n/a n/a
Standby Mode P
SB
kW n/a n/a n/a
Crankcase heater mode P
CK
kW n/a n/a n/a
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside conguration.
(6)
Please contact Airedale regarding Non Compliant selections