137 138 139
DCC082TR-19GYYV DCC084TR-20GYVV DCC087TR-21GVVV
FreeCooling No No No
Enhance Capital Allowance No No No
Number of Refrigeration Circuits 3 3 3
Cooling Duty - EC Fans
Nominal Output - Mechanical (1) kW 801.1 820.7 840.2
Nominal Input - Mechanical kW 261.8 265.7 269.6
EER (2) 3.06 3.09 3.12
ESEER 4.30 4.32 4.35
Nominal Output - Free Cooling kW N/A N/A N/A
Ambient temperature for
100% Free Cooling
(5) °C N/A N/A N/A
Capacity Steps %
10-25-35-45-55-
70-80-90-100
10-25-35-45-55-
70-80-90-100
10-25-35-45-55-
70-80-90-100
Minimum Turndown Ratio 0.11 0.11 0.12
Dimensions (H x W x L) mm 2682 x 2200 x 11638 2682 x 2200 x 11638 2682 x 2200 x 12770
Weight
Machine (3) kg 7425 7505 7880
Operating kg 8150 8230 8650
Water Volume (Total Internal) l 725 725 770
Maximum Waterow l/s 46.1 46.1 46.1
Minimum Waterow l/s 17.7 17.7 17.7
Face Area (Total) m² 2.38 2.38 2.38
Nominal Airow - EC Fans m³/s 122.4 128.9 135.3
Quantity 19 20 21
Maximum Speed - EC Fans rpm 1026 1026 1026
Compressor Trio + Trio + Trio Trio + Trio + Trio Trio + Trio + Trio
Quantity of Compressors 9 9 9
Oil Charge Volume (Total) l
3 x 5.3 + 3 x 5.3
+ 3 x 5.3
3 x 5.3 + 3 x 5.3
+ 3 x 5.3
3 x 5.3 + 3 x 5.3
+ 3 x 5.3
Refrigeration R410A / 2088
Charge (Total) kg 34 + 35 + 41 34 + 39 + 41 39 + 39 + 42
GWP Tonnes Equivalent CO2 tCO2 71 + 73 + 86 71 + 81 + 86 81 + 81 + 88
Refrigerant Control Electronic Expansion Valve (EEV)
Water Inlet / Outlet - Unit DN150 DN150 DN150
Water Drain / Bleed - Evap inch 1/2 1/2 1/2
Water System
Minimum System Water Volume (4) l 1563 1563 1668
Maximum System
Operating Pressure
Bar 10 10 10
DCC Mechanical Data - Regular Quiet
(1) Based on units performance at 12/7°C return/supply temperatures, 35°C ambient, 100% water. All performance data supplied in accordance with BBS EN14511-1:2013
(2) EER = DX Cooling Output / (Compressor input power + Fan Input Power),
(3) Based on standard unit without options, operating weight includes refrigerant charge and water volume.
For unit weights with waterside options tted please refer to Airedale.
(4) For minimum system volume, refer to Design Features & Information - Minimum System Water Volume Calculations
(5) Ambient temperature that full Freecool capacity can be achieved