128 129 130
Unit Data DCC088TR-15GVWW DCC091TR-15GWWW DCC074TR-17GPYY
Nominal Run Amps (1) A 609.1 621.2 493.3
Maximum Start Amps A 872.5 856.6 756.7
Recommended Mains Fuse Size A 630 670 560
Evaporator
Immersion Heater Rating W 250 250 250
Condenser Fan - Per Fan (EC)
Quantity 15 15 17
Full Load Amps A 3.9 3.9 3.9
Motor Rating kW 2.6 2.6 2.6
Compressor - Per Compressor
Nominal Run Amps A 55.2 / 59.2 / 59.2 59.2 / 59.2 / 59.2 59.2 / 47.9 / 47.9
Quantity 3 + 3 + 3 3 + 3 + 3 2 + 3 + 3
Motor Rating kW 33.1 / 36.2 / 36.2 36.2 / 36.2 / 36.2 36.2 / 29.8 / 29.8
Sump Heater Rating W 140 140 140
Start Amps (2) A 326 / 298 / 298 298 / 298 / 298 298 / 326 / 326
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98) (3)
Nominal Run Amps A 568.4 582.1 469.7
Reactive power reduction/saving (4) kVAr 72.3 70.2 44.2
Maximum Start Amps A 831.8 817.5 733.1
Recommended Mains Fuse Size A 630 670 560
Electronic Soft-start
Nominal Run Amps A 609.1 621.2 493.3
Maximum Start Amps A 742.1 737.4 626.3
Recommended Mains Fuse A 630 670 560
Power Factor Correction (PF
0.98) & Electronic Soft Start (3)
Nominal Run Amps A 568.4 582.1 469.7
Maximum Start Amps A 701.4 698.3 602.7
Recommended Mains Fuse Size A 630 670 560
Standard Head Pump (Single
or Run/Standby)
Pump Full Load Amps A 11.2 15.2 11.2
Unit Nominal Run Amps A 620.1 636.2 504.3
Recommended Mains Fuse Size A 670 670 560
Motor Rating kW 6.2 8.4 6.2
Larger Head Pump (Single
or Run/Standby)
Pump Full Load Amps A 21.2 21.2 21.2
Unit Nominal Run Amps A 630.1 642.2 514.3
Recommended Mains Fuse Size A 670 670 560
Motor Rating kW 12.1 12.1 12.1
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps A 10.2 13.9 10.2
Unit Nominal Run Amps A 617.2 632.3 501.6
Recommended Mains Fuse Size A 670 670 560
Motor Rating kW 6.4 8.6 6.4
Larger Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps A 19.8 19.8 19.8
Unit Nominal Run Amps A 625.0 637.2 509.5
Recommended Mains Fuse Size A 670 670 560
Motor Rating kW 12.4 12.4 12.4
(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold
DCC Electrical Data - Regular Quiet