EasyManua.ls Logo

AIREDALE DeltaChill - Page 199

AIREDALE DeltaChill
302 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technic al
Chillers
DeltaChill™ Air Cooled and FreeCool
199
Chiller Technical Manual 7267818 V1.13.0_01_2018
Air Cooled
137 138 139
Unit Data DCC082TR-19GYYV DCC084TR-20GYVV DCC087TR-21GVVV
Nominal Run Amps (1) A 551.3 579.6 608.0
Maximum Start Amps A 818.7 847.0 875.4
Recommended Mains Fuse Size A 630 630 630
Evaporator
Immersion Heater Rating W 250 250 250
Condenser Fan - Per Fan (EC)
Quantity 19 20 21
Full Load Amps A 3.9 3.9 3.9
Motor Rating kW 2.6 2.6 2.6
Compressor - Per Compressor
Nominal Run Amps A 47.9 / 47.9 / 55.2 47.9 / 55.2 / 55.2 55.2 / 55.2 / 55.2
Quantity 3 + 3 + 3 3 + 3 + 3 3 + 3 + 3
Motor Rating kW 29.8 / 29.8 / 33.1 29.8 / 33.1 / 33.1 33.1 / 33.1 / 33.1
Sump Heater Rating W 140 140 140
Start Amps (2) A 326 / 326 / 326 326 / 326 / 326 326 / 326 / 326
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98) (3)
Nominal Run Amps A 522.0 543.2 564.4
Reactive power reduction/saving (4) kVAr 54.1 65.3 76.6
Maximum Start Amps A 789.4 810.6 831.8
Recommended Mains Fuse Size A 630 630 630
Electronic Soft-start
Nominal Run Amps A 551.3 579.6 608.0
Maximum Start Amps A 688.3 716.6 745.0
Recommended Mains Fuse A 630 630 630
Power Factor Correction (PF
0.98) & Electronic Soft Start (3)
Nominal Run Amps A 522.0 543.2 564.4
Maximum Start Amps A 659.0 680.2 701.4
Recommended Mains Fuse Size A 630 630 630
Standard Head Pump (Single
or Run/Standby)
Pump Full Load Amps A 11.2 11.2 11.2
Unit Nominal Run Amps A 562.3 590.6 619.1
Recommended Mains Fuse Size A 630 630 670
Motor Rating kW 6.2 6.2 6.2
Larger Head Pump (Single
or Run/Standby)
Pump Full Load Amps A 21.2 21.2 21.2
Unit Nominal Run Amps A 572.3 600.6 629.1
Recommended Mains Fuse Size A 630 630 670
Motor Rating kW 12.1 12.1 12.1
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps A 10.2 10.2 10.2
Unit Nominal Run Amps A 559.6 587.8 616.1
Recommended Mains Fuse Size A 630 630 670
Motor Rating kW 6.4 6.4 6.4
Larger Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps A 19.8 19.8 19.8
Unit Nominal Run Amps A 567.5 595.5 623.8
Recommended Mains Fuse Size A 630 630 670
Motor Rating kW 12.4 12.4 12.4
(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold
DCC Electrical Data - Regular Quiet

Table of Contents

Related product manuals