ELECTRICAL DATA 149 150 151
Unit Data DCC058DX-12DVW0 DCC061DX-12DWW0 DCC050DX-14EPV0
Nominal Run Amps (1) A 409.7 421.8 354.8
Maximum Start Amps A 673.1 657.2 618.2
Recommended Mains Fuse Size A 450 450 400
Evaporator
Immersion Heater Rating W 170 170 170
Condenser Fan - Per Fan (EC)
Quantity 12 12 14
Full Load Amps A 3.9 3.9 3.9
Motor Rating kW 2.6 2.6 2.6
Compressor - Per Compressor
Nominal Run Amps A 55.2 / 59.2 59.2 / 59.2 59.2 / 55.2
Quantity 3 + 3 3 + 3 2 + 3
Motor Rating kW 33.1 / 36.2 36.2 / 36.2 36.2 / 33.1
Sump Heater Rating W 140 140 140
Start Amps (2) A 326 / 298 298 / 298 298 / 326
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98) (3)
Nominal Run Amps A 382.1 395.8 331.7
Reactive power reduction/saving (4) kVAr 48.9 46.8 41.2
Maximum Start Amps A 645.5 631.2 595.1
Recommended Mains Fuse Size A 450 450 400
Electronic Soft-start
Nominal Run Amps A 409.7 421.8 354.8
Maximum Start Amps A 542.7 538.0 487.8
Recommended Mains Fuse A 450 450 400
Power Factor Correction (PF
0.98) & Electronic Soft Start (3)
Nominal Run Amps A 382.1 395.8 331.7
Maximum Start Amps A 515.1 512.0 464.7
Recommended Mains Fuse Size A 450 450 400
Standard Head Pump (Single
or Run/Standby)
Pump Full Load Amps A 11.2 11.2 8.9
Unit Nominal Run Amps A 420.8 432.9 363.3
Recommended Mains Fuse Size A 450 450 400
Motor Rating kW 6.2 6.2 4.4
Larger Head Pump (Single
or Run/Standby)
Pump Full Load Amps A 11.2 11.2 11.2
Unit Nominal Run Amps A 420.7 432.8 365.8
Recommended Mains Fuse Size A 450 450 400
Motor Rating kW 6.1 6.1 6.1
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps A 10.2 10.2 7.3
Unit Nominal Run Amps A 417.9 430.1 360.6
Recommended Mains Fuse Size A 450 450 400
Motor Rating kW 6.4 6.4 4.5
Larger Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps A 10.1 10.1 10.1
Unit Nominal Run Amps A 417.8 430.0 362.9
Recommended Mains Fuse Size A 450 450 400
Motor Rating kW 6.3 6.3 6.3
(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold
DCC Electrical Data - Extra Quiet