XS4 SCALE HOUSING MANIFOLD/NODE: The Main
Profibus Cable travels from the AR15 Scale Driver
Control Node to the XS4 Scale Housing Manifold and
then out to the XS5 Infeed Housing Manifold.
(Illustration 141) The XS4 Scale Housing Manifold
sends Output signals to the directional valves that
release the Scale Seals and raise and lower the
Classifier Conveyors.
1. When all “Safety” conditions have been met, the
KA1/KA2 Relay energizes and sends 24 VDC
Control Voltage on wires 9 and common (2) to
pins 2 and 3 on the Power Cable Connector of
the XS4 Scale Housing Manifold Node.
(Illustration 141) This voltage is used to operate
the XS4 Node. If a guard is “opened, the
KA1/KA2 Relay will de-energize and there will
be no voltage to operate the XS4 Node.
2. The GS1 Power Supply sends 24 VDC Control
Voltage through the QF4 Circuit Breaker on
wires 7 and common (2) to pins 1 and 3 on the
Power Cable Connector of the XS4 Scale
Housing Manifold Node. This voltage is used to
operate the components controlled by the XS4
Node.
3. There is “no” Terminating Resistor on the XS4
Node.
4. The Address Setting for the XS4 Node must be
set correctly in order for the Node to operate.
(Illustration 142 )
IMPORTANT!
When replacing any of the Remote Nodes, the
“address setting” must be set correctly or the
Remote Node will not operate correctly! There will
be “NO” Profibus Communication between the
Computer and the Node. Refer to the “Profibus
Routing and Address Information” page of the
schematic for the correct address for each Node.