Installing the ETERNUS CS800 S5 Modules Installing the Components in the Rack
U41840-J-Z125-7-76 87
1. Identify the right and the left rail (see label or imprint on the rail).
2. Position the rail on the rear left support bracket by inserting the retaining bolts (1).
3. Press the rail together (2).
4. Move the rail outwards until the designated position (grid of support upright) is reached
(3).
The black bolts must lock in the corresponding holes.
5. Press the bracket backwards until the rail engages (4).
V
CAUTION!
The toothed levers must be closed.
The two black bolts must be flush with the bracket.
6. Check if the rail will be fixed by pressing the left rail backwards.
7. Repeat this procedure to install the right rail.
Option
Fix each rail with one earthquake security screw M5 (5). The earthquake security screw has
to be tightened with max. 1Nm.
Figure 44: Mounting the server onto the rack rails