Handling Instructions for the Rack Installing the Rack
90 U41840-J-Z125-7-76
Positioning the tilting protection
Slide the tilting protection under the rack so that it is in the center at the front.
Position the two front screw holes (1) of the tilting protection so that they are exactly
under the lozenge nuts (2).
Installing the tilting protection at the front
Lift the tilting protection slightly so that the screw holes align with the lozenge nuts.
Attach the tilting protection to the front of the rack with two supplied M6 x10 mm
countersunk screws (1).
Torque: 5.2 Nm
3
3
1
2
2
1
11