Operation - Stream Configuration
Part No.: 4418309_Rev09 Fusion4 MSC-L
Honeywell Installation & Operation Manual 5 - 167
5.14.1.5.0.5 Block Valve
On the Stream Config . Stream n . Alarms screen, select <Block valve>.
The Stream Config . Stream n . Block valve screen appears.
5.14.1.5.0.5.1 Block Valve fault
On the Stream Config . Stream n . Block valve screen, select <Block
valve fault>.
The Stream Config. . Stream n . Block Valve fault screen is displayed
with the following entities.
[Pump feedback timeout]
With this entity you can set the time in
seconds in which the product stream
hydraulic pump must give feedback to
the MSC-L. If no hydraulic pump
feedback is received in
[Pump
feedback timeout], an alarm occurs
depending on the
[Alarm action].
<1> s ... <255> s
(default = <15> s)
Entity Description Value range
[Alarm action]
With this entity you can configure the
alarm behavior, in case this particular
alarm occurs.
<Disabled>
<Display>
<Display shutdown>
<Display pause>
[Feedback timeout]
With this entity you can set the time in
seconds in which the product stream
block valve must give feedback to the
MSCL. If no feedback is received in
[feedback timeout] an alarm occurs
depending on
[Alarm action].
<1> s ... <255> s
(default = <15> s)
Entity Description Value range