Operation - Calibration
Fusion4 MSC-L Part No.: 4418309_Rev09
5 - 268 Installation & Operation Manual
Honeywell
place (for example, to observe the result) until the process
continues.
7. Enter the start delay in seconds and then select <Confirm>.
The Calibration . Arm n . Stream n. Wizard screen appears with
the Preset volume, Flowrate, Start delay time in seconds, and
the Metered Volume.
8. Select <OK> on the IR controller or LAD to start the calibration.
The countdown of the delay time starts. After the expiration of
the delay time, the calibration process starts.