Item Alarm Severity
Selection
Description
Critical, Major,
Minor, Warning
NOTE
Critical: red light
Major: orange light
Minor: yellow light
Warning: white light
None The eLight strip light is steady
blue (atmosphere light).
NOTE
After you set the alarm severity, the eLight indicator is o if no alarm is generated.
Step 4 If there are multiple eLights, repeat Step 1Step 3.
----End
5.8 Commissioning the PDU2000 (for
FusionModule800)
When the system type is FusionModule800 and a PDU2000 is installed, perform
the following steps to
congure it.
Prerequisites
One end of the straight-through cable has been connected to the COM port on
the PDU2000 and the other end has been connected to the COM port on the ETH
converter.
Context
Table 5-12 PDU2000 basic Information
Vendor
Name
Displayed on
the WebUI
Eleventh and Twelfth
Characters in Device
Barcode
a
Clever PDU2000-M(C) FT
Haipengxin PDU2000-M(H) 6B
a: The barcode starts with 21 and is attached to the device.
Procedure
Step 1 Set the PDU2000 monitoring parameters.
Set the PDU2000-M (C) monitoring parameters.
ECC800 Data Center Controller
User Manual (for ECC800-Pro) 5 Power-On Commissioning
Issue 02 (2020-09-07) Copyright © Huawei Technologies Co., Ltd. 120