Table 6-34 Fire sensor NO and NC denitions
Item Denition
NO Dry contact signal for the re sensor
abnormality alarm. Closed: alarm;
open: normal
NC Dry contact signal for the re sensor
abnormality alarm. Closed: normal;
open: alarm
4. Click Submit.
----End
Follow-up Procedure
After the alarm has been cleared when re control linkage or smoke alarm
linkage occurs, perform the following operations:
● Close the skylight manually.
● Start the smart cooling products manually.
● After turning o the lights, set Set light mode of the AC actuator to
Automatic. WebUI path: Monitoring > Aisle > AC Actuator Group > AC
Actuator > Running Parameters.
When a smart module actuator is congured, you need to set parameters for the
smart module actuator. The setting process is similar.
6.6.1.2 High Temperature Linkage
Context
● The ECC800-Pro implements high temperature linkage. If it detects high
temperature alarms by interacting with multi-functional sensors and all smart
cooling products fail to communicate with the ECC800-Pro, the ECC800-Pro
opens skylights based on the alarm status to facilitate heat dissipation.
● The default status of high temperature linkage is
o. Set it based on the
actual situation.
Procedure
Step 1 Log in to the ECC800-Pro WebUI as an administrator.
Step 2 Choose System Settings > Linkage Control.
Step 3 Ensure that Enable linkage control function is Yes.
Step 4 Ensure that Link high temperature with skylight open is in on state on the
Linkage Group tab page.
ECC800 Data Center Controller
User Manual (for ECC800-Pro) 6 Feature Description
Issue 02 (2020-09-07) Copyright © Huawei Technologies Co., Ltd. 191