6.6.1 FusionModule2000 Linkage Control
Prerequisites
You have obtained the IP address of the ECC800-Pro as well as the user name
and password used for WebUI login.
A PC with an IP address in the same network segment as that of the ECC800-
Pro is prepared, and the PC has connected to port WAN1 on the ECC800-Pro.
Ensure that Enable linkage control function is Yes.
Linkage Grouping
Table 6-33 FusionModule2000 linkage grouping
Linkage Category Default Status Function
Link smoke alarm
with skylight open
Open door/turn on
lights if smoke
alarm
a
on If a smoke alarm is raised, the
smart module opens the skylights,
access control, and lights by
default.
Link smoke alarm with
air conditioner o
o If this linkage status is set to on
and a smoke alarm is raised, the
smart cooling products turn o
automatically.
Intelligent lighting
a
o If this linkage status is set to on,
an infrared alarm is raised when
the camera detects human motion,
and the aisle lights turn on
automatically for authorized door
opening.
Link re control
with skylight open
Open door/turn on
lights by re linkage
a
Link
re control
with air conditioner
o
o If you set this linkage status to on
and a re occurs in the smart
module, the skylights open, lights
turn on, and the access control
opens automatically, or the smart
cooling products turn
o
automatically.
Link high temperature
with skylight open
o If this linkage status is set to on,
the skylights open automatically
when a high temperature alarm is
raised and all smart cooling
products fail to communicate with
the ECC800-Pro.
ECC800 Data Center Controller
User Manual (for ECC800-Pro) 6 Feature Description
Issue 02 (2020-09-07) Copyright © Huawei Technologies Co., Ltd. 188