6.4.3 Commissioning the Exit Button, Skylight Button,
Atmosphere Light, Emergency Button, and Magnetic Lock
Procedure
Step 1 Check functions of the exit button.
Table 6-12 Function commissioning
Check Method Normal Connection Status
Attempt to open the door by pressing
the exit button when the aisle door is
closed.
The aisle door is opened successfully.
Step 2 Check functions of the skylight button.
Table 6-13 Function commissioning
Check Method
Normal Connection Status
Attempt to open the door by pressing
the skylight button when the aisle
door is closed.
The skylight can be opened manually.
Step 3 Check functions of the atmosphere light.
Table 6-14 Function commissioning
Check Method
Normal Connection Status
Press the atmosphere
light button.
The atmosphere light is steady blue.
Step 4 Check functions of the emergency button.
Table 6-15 Function commissioning
Check Method
Normal Connection
Status
Follow-up Procedure
Attempt to open the door
by pressing the emergency
button when the aisle
door is closed.
The aisle door is
opened successfully.
You need to restore the
emergency button.
ECC800 Data Center Controller
User Manual (for ECC800-Pro) 6 Feature Description
Issue 02 (2020-09-07) Copyright © Huawei Technologies Co., Ltd. 141