Indicator Color Name Status Description
Blinking The indicator blinks at
super short intervals for
0.5s (blinking at 10 Hz, on
for 0.05s and then o for
0.05s) and then turns o
for 0.5s. The cycle lasts for
5s.
ALM Red Alarm
indicator
Steady on The PoE output current is
overloaded.
O The PoE output is normal
or not connected.
3.2.4 Access Control System
The access control system applies to the equipment rooms, aisle containment, and
cabinet doors.
3.2.4.1 Aisle Access Control System
The access control system collects and monitors data about the access of devices
and personnel to ensure access security.
Diverse access control devices such as the
ngerprint and card reader with a
keypad,
ngerprint and card reader, and card reader with a keypad are supported.
Note that the communication distance between an access control device and an
access actuator should be less than or equal to 5 meters.
If the IC cards used by the access control device need to be purchased, the IC card chip
specications are as follows.
Table 3-27 IC card chip specications
Item
Specications
Chip model S50
Chip name Mifare 1K (S50) card
Chip type Philips Mifare 1 IC S50
Operating frequency 13.56 MHz
Read/write distance 1–3 cm
Storage capacity 8 kbit, 16 partitions
ECC800 Data Center Controller
User Manual (for ECC800-Pro) 3 Device Description
Issue 02 (2020-09-07) Copyright © Huawei Technologies Co., Ltd. 32