Path Parameter Setting
devices are
displayed.
Communicati
ons Port
Select COM1 from the drop-down list box.
NOTE
The setting example indicates that the device
connects to the COM1 port on the ECC800-Pro.
If the device connects to another port, enter the
number of the connected port.
Device
Address
This section uses 1 as an example. In
practice, set this parameter to be the same
as the communications address for the
device.
3. Click Test Connect to check whether the device connects to the ECC800-Pro
properly.
– If the independent deployment AI_DI unit connects to the ECC800-Pro
successfully, click
Conrm. The connected devices are displayed in the
Number of connected devices list.
– If the connection fails, check whether the device is properly connected to
the ECC800-Pro, whether the device and ECC800-Pro are running
properly, and whether the parameter settings are consistent with the
device parameters.
----End
Follow-up Procedure
Choose Home > Plan View on the ECC800-Pro WebUI, and drag the device to the
corresponding position in the Smart Module View pane based on the actual
device layout.
8.1.30 How Can I Add Devices Accessed Through the ECC800-
Pro AI/DI Port to the ECC800-Pro WebUI?
Prerequisites
This section uses the device connecting to the AI/DI_3 port on the ECC800-Pro as
an example.
ECC800 Data Center Controller
User Manual (for ECC800-Pro) 8 FAQ
Issue 02 (2020-09-07) Copyright © Huawei Technologies Co., Ltd. 333