Procedure
Step 1 Apply for a xed IP address to the equipment room network administrator.
Step 2 Set the IP address, subnet mask, and default gateway on the ECC800-Pro WebUI.
Table 6-51 IP parameters
Path Parameter Default
Value
Setting
System
Settings >
System
Parameter
s >
Monitor IP
> WAN_1
IP 192.168.8.1
0
Set this parameter based on the IP
address assigned by the network
administrator.
Subnet
mask
255.255.25
5.0
Set this parameter based on the
subnet mask assigned by the network
administrator.
Default
gateway
192.168.8.1 Set this parameter based on the
default gateway address assigned by
the network administrator.
Step 3 Click Submit.
Step 4 Set NetEco communications parameters and authentication password on the
ECC800-Pro WebUI.
Table 6-52 NetEco parameters
Path
Parameter Default
Value
Setting
System
Settings >
NMS
Application
> NetEco >
Communicat
ion
Parameters
NetEco
Location
Local Set this parameter based on the
type of the connected NetEco
management system.
Local: NetEco
Cloud: CloudOpera NetEco
Server IP 192.168.8.
11
IP address of the primary NetEco
server
NOTE
The NetEco IP address and the ECC800-
Pro IP address must be
congured in
the same network to ensure normal
connection between the NetEco and
the ECC800-Pro.
Port number 31220 31220
Link to the
monitoring
IP address
WAN_1 WAN_1
ECC800 Data Center Controller
User Manual (for ECC800-Pro) 6 Feature Description
Issue 02 (2020-09-07) Copyright © Huawei Technologies Co., Ltd. 236