Table 8-1 Setting a device address
Devic
e
Addre
ss
Toggl
e
Switc
h 1
Toggl
e
Switc
h 2
Toggl
e
Switc
h 3
Toggl
e
Switc
h 4
Toggl
e
Switc
h 5
Toggl
e
Switc
h 6
Toggl
e
Switc
h 7
Toggl
e
Switc
h 8
1 ON OFF OFF OFF OFF OFF OFF OFF
2 OFF ON OFF OFF OFF OFF OFF OFF
3 ON ON OFF OFF OFF OFF OFF OFF
4 OFF OFF ON OFF OFF OFF OFF OFF
Set monitoring parameters for UPS2000G-A-(6 kVA–20 kVA).
NO TE
Operate the DIP switch S2 on the optional Modbus card to set the UPS2000G-A device
address. Toggle switches 1 to 8 of DIP switch S2 specify the device address in binary mode.
ON indicates 0, and OFF indicates 1.
Table 8-2 Setting a device address
Devic
e
Addre
ss
Toggl
e
Switc
h 1
Toggl
e
Switc
h 2
Toggl
e
Switc
h 3
Toggl
e
Switc
h 4
Toggl
e
Switc
h 5
Toggl
e
Switc
h 6
Toggl
e
Switc
h 7
Toggl
e
Switc
h 8
1 OFF ON ON ON ON ON ON ON
2 ON OFF ON ON ON ON ON ON
3 OFF OFF ON ON ON ON ON ON
4 ON ON OFF ON ON ON ON ON
Step 2 Add a UPS2000G-A.
1. Log in to the ECC800-Pro WebUI as an administrator.
2. Add a UPS2000G-A.
Table 8-3 Adding a UPS2000G-A
Path
Parameter Setting
Choose
System
Settings >
Device
Management
and click Add
Device. The
parameters
Device
attribute
Select UPS from the drop-down list box.
Device Type Select UPS2000G-A from the drop-down
list box.
Connect To Select ECC800 from the drop-down list
box.
ECC800 Data Center Controller
User Manual (for ECC800-Pro) 8 FAQ
Issue 02 (2020-09-07) Copyright © Huawei Technologies Co., Ltd. 263