2. Choose System Info > Settings, enter the user name admin and password
000001, and tap . In the displayed dialog box for conrming the
password, tap Conrm.
3. Tap Communication and check IP address assign to Manual. And set Serial
port baud rate to 9600, and Serial port address to 1 on the displayed
communication settings screen.
Figure 8-11 PDU8000 communication settings screen
Step 2 Add a PDU8000 (Modbus-RTU).
1. Log in to the ECC800-Pro WebUI as an administrator.
2. Add a PDU8000.
Table 8-12 Adding a PDU8000
Path
Parameter Setting
Choose
System
Settings >
Device
Management
and click Add
Device. The
parameters
for adding
devices are
displayed.
Device
attribute
Select PDU from the drop-down list box.
Device Type Select PDU8000 from the drop-down list
box.
Connect To Select ECC800 from the drop-down list
box.
Communicati
ons Port
Select COM1 from the drop-down list box.
NOTE
The setting example indicates that the
PDU8000 is connected to the COM1 port on the
ECC800-Pro. If the PDU8000 is connected to
another port, enter the number of the
connected port.
ECC800 Data Center Controller
User Manual (for ECC800-Pro) 8 FAQ
Issue 02 (2020-09-07) Copyright © Huawei Technologies Co., Ltd. 276