7 Function Code Table NICE3000
new
User Manual
- 180 -
Function
Code
Parameter Name Setting Range Default Unit Property Page
F8-16
Start address of
hall call auxiliary
command
0–40 0 -
☆
227
F8-17
Hall call address
check
0–1 0 -
☆
227
Group F9: Time parameters
F9-00
Idle time before
returning to base oor
0–240 10 min
☆
217
F9-01
Time for fan and lamp
to be turned off
0–240 2 min
☆
227
F9-02
Motor running time
limit
0–45 45 s
★
228
F9-03 Clock: year 2000–2100
Current
year
YYYY
☆
228
F9-04 Clock: month 1–12
Current
month
MM
☆
228
F9-05 Clock: day 1–31 Current day DD
☆
228
F9-06 Clock: hour 0–23
Current
hour
HH
☆
228
F9-07 Clock: minute 0–59
Current
minute
MM
☆
228
F9-09
Accumulative running
time
0–65535 0 h
●
228
F9-11
High byte of running
times
0–9999 0 -
●
228
F9-12
Low byte or running
times
0–9999 0 -
●
228
F9-13
Maintenance
notication period
0–99 0 day
★
228
Group FA: Keypad setting parameters
FA-00
Keypad display
selection
0: Reversed display of physical
oor
1: Positive display of physical
oor
2: Reversed display of hall call
oor
3: Positive display of hall call oor
3 -
☆
244
FA-01
Display in running
state
1–65535 65535 -
☆
229
FA-02 Display in stop state 1–65535 65535 -
☆
230
FA-03 Current encoder angle 0.0–359.9 0.0
Degree
(°)
●
243
FA-05 MCB board software 0–65535 0 -
●
243
FA-06 Drive board software 0–65535 0 -
●
243
FA-07 Heatsink temperature 0–100 0 °C
●
243