NICE3000
new
User Manual 9 Troubleshooting
- 279 -
9
Fault
Code
Name Possible Causes Solution
Level
Err43
Up limit signal
abnormal
Subcode 101: The up limit
switch acts when the elevator
is running in the up direction.
Subcode 101:
Check the signal feature (NO, NC) of the
up limit switch.
Check whether the up limit switch is in
good contact.
Check whether the limit switch is
installed at a relatively low position and
acts even when the elevator arrives at
the terminal oor normally.
4C
Err44
Down limit
signal abnormal
Subcode 101: The down
limit switch acts when the
elevator is running in the down
direction.
Subcode 101:
Check the signal feature (NO, NC) of the
down limit switch.
Check whether the down limit switch is in
good contact.
Check whether the limit switch is
installed at a relatively high position and
thus acts even when the elevator arrives
at the terminal oor normally.
4C
Err45
Slow-down
switch
abnormal
Subcode 101: The down
slow-down distance is
insufcient during shaft
auto-tuning.
Subcode 102: The up
slow-down distance is
insufcient during shaft
auto-tuning.
Subcode 103: The slow-
down switch is stuck or
abnormal during normal
running.
Subcodes 101 to 103:
Check whether the up slow-down switch
and the down slow-down switch are in
good contact.
Check the signal feature (NO, NC) of the
up slow-down switch and the down slow-
down switch.
Ensure that the obtained slow-down
distance satises the slow-down
requirement at the elevator speed.
4B
Err46
Re-leveling
abnormal
Subcode 101: The leveling
signal is inactive during
re-leveling.
Subcode 102: The re-
leveling running speed
exceeds 0.1 m/s.
Subcode 103: At startup of
normal-speed running, the
re-leveling state is valid
and there is shorting door
lock circuit feedback..
Subcode 104: During
re-leveling, no shorting
door lock circuit feedback
or door lock signal is
received 2s after shorting
door lock circuit output.
Subcode 101: Check whether the leveling
signal is normal.
Subcode 102: Check whether the encoder is
used properly.
Subcodes 103, 104:
Check whether the signal of the leveling
sensor is normal.
Check the signal feature (NO, NC) of the
feedback contact on the shorting door
lock circuit contactor, and check the relay
and wiring of the SCB-A board.
2B