User Manual 9 Troubleshooting
- 283 -
Fault
Code
Name Possible Causes Solution
Level
Err58
Shaft position
switches
abnormal
● Subcode 101: The
up slow-down switch
and down slow-down
switch are disconnected
simultaneously.
● Subcode 102: The
up limit feedback and
down limit feedback
are disconnected
simultaneously.
Subcodes 101, 102:
● Check whether the signal feature (NO,
NC) of the slow-down switches and
limit switches are consistent with the
parameter setting of the MCB.
● Check whether malfunction of the slow-
down switches and limit switches exists.
4B
Err62
Analog input
cable broken
Subcode 101:
The current car load (F8-05)
is smaller than the car no-load
load (F8-06) and the deviation
is larger than the threshold.
Subcode 101:
● Check whether F5-36 is set correctly.
● Check whether the analog input cable of
the CTB or MCB is connected incorrectly
or broken.
● Adjust the load cell switch function.
1A
● Fault Err41 is not recorded in the elevator stop state.
● Fault Err42 is reset automatically when the door lock circuit is shorted or 1s after the fault occurs in
the door zone.
● If faults Err51, Err52, and E57 persist, they are recorded once every one hour.