9 Troubleshooting NICE3000
new
User Manual
- 282 -
9
Fault
Code
Name Possible Causes Solution
Level
Err53
Door lock fault
Subcode 101: The door
lock feedback signal
remains active 3s after
door open output.
Subcode 102: The states
of the door lock multi-way
feedback contacts are
inconsistent 3s after door
open output.
Subcode 103: Reserved.
Subcode 104: The higher-
voltage and low-voltage
door lock signals are
inconsistent.
Subcode 101:
Check whether the door lock circuit is
normal.
Check whether the feedback contact of
the door lock contactor acts properly.
Check whether the system receives the
door open limit signal when the door lock
signal is valid.
Subcode 102:
Check whether when the hall door lock signal
and the car door lock signal are detected
separately, the detected states of the hall
door locks and car door lock are inconsistent.
Subcode 104:
When the higher-voltage and low-voltage
door lock signals are detected at the
same time, the time when the MCB
receives the two signals has a deviation
of above 1.5s. This causes system
protection.
This subcode is reset at power-off and
power-on again.
5A
Err54
Overcurrent
at inspection
startup
Subcode 101: reserved
Subcode 102: The current
at startup for inspection
exceeds 120% of the rat-
ed current.
Subcode 102:
Reduce the load
Change Bit1 of FC-00 to 1 to cancel the
startup current detection function.
5A
Err55
Stop at another
landing oor
Subcode 101: During
automatic running of the
elevator, the door open limit
is not received within the time
threshold in Fb-06.
Subcode 101: Check the door open limit
signal at the present oor.
1A
Err57
Serial
peripheral
interface (SPI)
communication
abnormal
Subcodes 101, 102: The
SPI communication is
abnormal. No correct data
is received with 2s of DSP
communication.
Subcode 103: The MCB
does not match the AC
drive.
Subcodes 101, 102:
Check the wiring between the control board
and the drive board.
Subcode 103:
Contact us or directly our agent.