Voltage Transformer
5 - 7
Vprim is measured and displayed.
To save the measurement press K
EEP RESULTS.
Navigate to the "V sec" entry field.
Enter the measured Vsec value either by turning the handwheel or by
entering this value with the numerical keys, and press E
NTER or the
handwheel to acknowledge your setting.
The ratio is calculated and displayed.
To stop the manual test, press the I/O (test start/stop). The test can now be
assessed.
To repeat the test, first press B
ACK TO T OP, if applicable, and then C LEAR
R
ESULTS.
To learn more about test assessment, refer to ”Test Assessment” on page 10-2.
Note: Alternatively, it is possible to enter the manually measured value
into the test card after the test was stopped (for example, if the
measurement was carried out at a remote location).