Others - Sequencer
8 - 7
Press the A
DD STATE button, and repeat steps to to define additional
states. Note that the maximum possible number of states is 7.
Sequencer differentiates two "Overload" trigger conditions:
– the occurrence of an overload (as described above)
– the clearing of an overload condition.
Note: Clearing of an overload condition means: the CB closes
again. For debouncing purposes, at CB closing time
measurements, CPC 100 adds a fixed time of 100ms to the
measured value. In order to determine the true CB closing time
value, these 100ms need to be deducted from the value displayed
in the measurement table (refer to the following examples).
The feature M
ANUAL TRIGGER provides a possibility to manually
initiate a trigger signal (that is, a premature termination) of the current
state at any time. This manual trigger has the same function as an
automatic trigger signal.
Trigger threshold.
Only available if a trigger ">" or "<" was selected (refer to ).
State duration. After this period of time the state terminates and the
sequence continues with the next state (if any). If a trigger signal occurs
before this time has elapsed, the currently running state terminates and
the sequence continues with the next state. If "SOOT" is selected, the
trigger signal terminates the complete sequence.
The default state duration time is 2s.
A current state has a minimal time of 250ms if the "Repeat" check box is
cleared.
Note: Do not set the state duration shorter than 500 ms if the "Repeat"
check box is selected.
A voltage state has a minimal time of 2s.
Setting a time of 0.000s makes the state infinite. Only a trigger signal will
terminate it.