Getting Started with Quick
3 - 5
After having pressed K
EEP RESULTS, the combo box for the calculated
quantity is disabled, that is, the calculated quantities cannot be changed.
V I Rs, Ls or Rp, Cp:
Resistance R and either inductance Ls in H
(series equivalent circuit) or capacity Cp
in F (parallel equivalent circuit).
This is just another representation of the
impedance Z
measurement; Z is displayed
in its components.
Using Rs, Ls, the impedance is given by:
Z
=Rs+jω Ls, where ω =2π f and the set
frequency is used for the calculation.
Using Rp, Cp, the admittance is given by:
1/Z
=1/Rp+jω Cp, where ω =2π f and
the set frequency is used for the
calculation.
Measured
quantities
Display of calculated value in
measurement table
(m1) (m2)

Table of Contents