7.1 Basic Operation
7-7
7.1.5 Setting and Operation of J-point Control
• JOG positioning (J-point) control operates at target speed until the start contact of J-point
positioning turns ON after the operation of the positioning unit starts, and the next positioning
control will start when the start contact of J-point positioning turns ON.
Settings
Items
Setting example
Table 1
J-point
axis parameter
setting
Table 2 Table 3
Operation pattern
J: Speed point
−
P: Pass point E: End point
Control method
I: Increment
−
I: Increment I: Increment
X-axis movement
amount
5000 pulses
−
10000 pulses 3000 pulses
Acceleration/dece
pattern
L: Linear
−
L: Linear L: Linear
Acceleration time (ms)
100 ms
−
200 ms 30 ms
Deceleration time (ms)
10 ms
−
20 ms 150 ms
Target speed
10000 pps
−
20000 pps 5000 pps
J-point control code
−
Linear acceleration/
deceleration
− −
J-point acceleration time
−
10 ms
− −
J-point deceleration time
−
10 ms
− −
J-point target speed
−
30000 pps
− −
• Specify parameters for the start of operation in the positioning data table.
Specify parameters in the axis parameter-setting menu at the time of speed
change.
• J-point control can be used for single-axis control only. It is not available
for interpolation control.
• Set the positioning unit to increment mode to implement P-point control, C-
point control, or E-point control with positions specified after J-point
control is implemented.
• Speed control is performed while the positioning unit is in J-point control,
in which case, be sure to input the amount of movement for positioning with
a value that can secure a target constant-speed area.