Because RFL™ and Hubbell® have a policy of continuous product improvement, we reserve the right to change designs and specifications without notice.
9.2.2 SPECIFICATIONS
As of the date this manual was published, the specifications shown in Table 9-2 apply to all 2000 PS
power supply modules, except where indicated. Because all RFL products undergo constant refinement
and improvement, these specifications are subject to change without notice.
Table 9-2. IMUX 2000 M-DACS Power Supply Specifications
High Power
Power
Supply→
Specifications
↓
9547-840
(250Vdc)
9547-930
(220Vac)
9547-965
(48-125Vdc)
9547-975
(24Vdc)
9547-985
(120Vac)
Input Voltage
Range
200 to 300 Vdc 180 to 265 Vac 38 to 150 Vdc 19 to 29 Vdc 88 to 132 Vac
Max Output
Current:
+5V
+15V
-15V
-48V
5.00A
0.75A
0.75A
0.10A
4.00A
1.00A
0.75A
0.10A
6.00A
1.75A
1.00A
0.10A
Adjustments:
R44
R49
R50
R61
R76
NA
NA
NA
Output adjust
+5V output adjust
+5 Volt output adjust
+15 Volt output adjust
-15 Volt output adjust
NA
NA
NA
NA
NA
Output adjust +5V/+15V/-15V
NA
Test Points:
TP1
TP2
TP3
TP4
TP5
TP6
TP7
TP8
M-DACS-T1 RFL Electronics Inc.
TP9
TP10
+15 Volt output
Output circuit common
-15 Volt output
+5 Volt output
NA
Input circuit common
Output circuit common
+5Volt output
+15 Volt output
-15 Volt output
-48Vdc output
NA
FET gate drive NA
NA
NA
Supply voltage (Vcc) to PWM
Input to +15Vdc regulator
-48Vdc output NA
Indicators
DS1 – Normal (Green)
DS2 – Alert (Yellow)
DS3 – Fail (Red)
DS4 – Power (Green)
DS5 – Supply Fail (Red)
Alarm Disable
Switch
Enables “dropout” of relays K51 & K52 on Power Supply Alarm I/
O module when in the ENABLE position. Keeps
relays K51 & K52 on Power Supply Alarm I/O moduile “pulled in” when in the DISABLED position.
SW1
Operating
Temperature
-20
o
C to +65
o
C
Humidity
95% @ +40
o
C
Isolation 2500 Vdc isolation from input terminals to ground, output terminals to ground, input terminals to output terminals,
relay contacts to ground, and relay contacts to coil.
August 7, 2012 9-2 (973) 334-3100